Using Multi-Drive Mode

Chapter 7

Automatic Device Replacement (ADR) cannot be used with any of the
drives.

The RSNetWorx Parameter editor cannot be used to access the

Host

parameters. It can only access the parameters on the DeviceNet adapter.

Since the RS-485 ports are used for daisy-chaining the drives, there is no
connection for a peripheral device such as a HIM or USB converter
module (1203-USB). DSI Splitter cables cannot be used to add a second
connection for a peripheral device.

System Wiring

To daisy-chain the drives of the PowerFlex 525, the AK-U0-RJ45-TB2P terminal
block connector can be used for easy installation.

The wiring diagram for using AK-U0-RJ45-TB2P terminal block connectors is
shown below.

The AK-U0-RJ45-TB2P comes with (5) terminal block connectors and (2)
terminating resistors.

Understanding the I/O Image

The terms

input and output are defined from the scanner’s point of view.

Therefore, Output I/O is data that is output from the scanner and consumed by
the adapter. Input I/O is status data that is produced by the adapter and
consumed as input by the scanner.

The I/O image table will vary based on the configuration of

Host parameters

C169 [MultiDrv Sel]

and C175 [DSI I/O Cfg]. The image table always uses

consecutive words starting at word 0.

The

Multi-Drive Example of I/O Image on page 72

for an illustration of the

Multi-drive I/O image with 16-bit words.

To PowerFlex 525 with
DeviceNet adapter

To Drive #2

To Drive #3

To Drive #4

To Drive #5

120