beautypg.com

Rockwell Automation 25-COMM-D PowerFlex 525 DeviceNet Adapter User Manual

Page 39

background image

Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013

39

Configuring the I/O

Chapter 4

As the selected DeviceNet path is browsed, RSNetWorx for DeviceNet
software creates a graph view window that shows a graphical
representation of the devices on the network.

If the icon for the drive (for this example, PowerFlex 525) on the network
appears as Unrecognized Device, use RSNetWorx for DeviceNet software
to create the PowerFlex 520-series drive EDS file. See

Create the EDS File

from Online Device on the Network on page 39

or

Download the EDS

File from the Internet Web Site on page 40

for instructions on how to

create the EDS file.

Create the EDS File from Online Device on the Network

1.

Right-click the Unrecognized Device icon and select Register Device in
the menu. The EDS Wizard appears.

2.

Click Next to start creating the EDS file.

3.

Select Create an EDS file.

4.

Click Next.
If the EDS file is already downloaded and resides on your computer, select
“Register an EDS file” and click Next. Then follow the screen prompts and
disregard the remaining steps (5...13) in this procedure.

5.

Enter a description (if desired).

This manual is related to the following products: