Additional information, Parameter read message configuration on, Parameter write message configuration on – Rockwell Automation 25-COMM-D PowerFlex 525 DeviceNet Adapter User Manual

Page 83

background image

Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013

83

Using Multi-Drive Mode

Chapter 7

Parameter Read Message Configuration

Parameter Write Message Configuration

The Class Code is “f ” for the Parameter Object and the Instance Attribute is “1”
to select retrieving the parameter value. See

Appendix C

,

Parameter Object

for

more information. The Instance value is “18541” to access parameter P109
[Accel Time 1]

in the first daisy-chained drive.

The Explicit message for Drive 1 to Drive 4 are identical except for the Instance
values, see

Multi-Drive Mode Explicit Messaging on page 82

for examples.

Additional Information

When the PowerFlex 525 drive with the 25-COMM-D DeviceNet
adapter (Drive 0) is powered up, all configured daisy-chained drives must
be present before an I/O connection is allowed on DeviceNet (i.e. before
the drives can be controlled).

If the PowerFlex 525 drive with the 25-COMM-D DeviceNet adapter
(Drive 0) is powered down, communications with the four daisy-chained
drives (Drive 1 to Drive 4) are disrupted and the drives will take their
corresponding Comm Loss Actions.