Dpi parameter object, Class code, Instances – Rockwell Automation 25-COMM-D PowerFlex 525 DeviceNet Adapter User Manual
Page 117: Class attributes, Class code instances
![background image](/manuals/577523/117/background.png)
Rockwell Automation Publication 520COM-UM001A-EN-E - April 2013
117
DeviceNet Objects
Appendix C
DPI Parameter Object
Class Code
Instances
The number of instances depends on the number of parameters in the device.
The total number of parameters can be read in Instance 0, Attribute 0.
Class Attributes
Hexadecimal
Decimal
0x93
147
Instances (Hex.)
Instances (Dec.)
Single-Drive Mode
Multi-Drive Mode
0x0000...0x3FFF
0...16383
Instances 0...1023 in the drive
Instances 0...1023 in Drive 0
0x4000...0x43FF
16384...17407
Instances 0...1023 in the adapter
Instances 0...1023 in the adapter
0x4400...0x47FF
17408...18431
DSI
Instances 0...1023 in Drive 1
0x4800...0x4BFF
18432...19455
Option
Instances 0...1023 in Drive 2
0x4C00...0x4FFF
19456...20479
Not supported
Instances 0...1023 in Drive 3
0x5000...0x53FF
20480...21503
Not supported
Instances 0...1023 in Drive 4
0x5400...0x57FF
21504...22527
Not supported
Instances 0...1023 in the Option
Attribute ID
Access Rule
Name
Data Type
Description
0
Get
Number of Instances
UINT
Number of parameters in the device
1
Set
Write Protect Password
UINT
0 = Password disabled
n = Password value
2
Set
NVS Command Write
USINT
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
4 = Partial defaults
5 = System defaults
3
Get
NVS Parameter Value Checksum
UINT
Checksum of all parameter values in a user set in NVS
5
Get
First Accessible Parameter
UINT
First parameter available if parameters are protected by passwords. A “0”
indicates all parameters are protected.
7
Get
Class Revision
UINT
2 = DSI