Commissioning
Evaluating and retracting from hardware limit switch
Evaluating hardware limit switches
l
172
EDBCSXM064 EN 11.0
6.17
Evaluating and retracting from hardware limit switch
6.17.1
Evaluating hardware limit switches
ƒ
Ensure a fail−safe design of the hardware limit switches (NC contact, LOW active).
ƒ
The active level is set with C0114/x.
ƒ
A response to active hardware limit switches can be set via C3175.
ƒ
If a hardware limit switch is activated, the drive reacts as set and a fault message is
displayed.
Positive hardware limit switch is activated:
– Fault no. x400 ("Pos HW End")
– Status bit 5 = 1
Negative hardware limit switch is activated:
– Fault no. x401 ("Neg HW End")
– Status bit 6 = 1
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C3175 HW EndReac
4
Reaction, when a hardware limit
switch is activated.
^ 172
0
TRIP
1
Message
2
Warning
3
Off
4
FAIL−QSP
6.17.2
Retracting from hardware limit switches
1. Only with user software
£1.x(A−SW see nameplate):
Deactivate limit switch monitoring: Ctrl1.Bit1 = 1 (TRUE)
Retracting from an activated hardware limit switch is enabled.
2. Reset fault message: Set Ctrl1.Bit11 = 1.
3. Activate operating mode: Ctrl1.Bit12 = 1 (TRUE)
)
Note!
For retracting, return the drive to the travel range. The active hardware limit
switch must not be overtravelled while retracting.
ƒ
Positive hardware limit switch is active
W Retracting in negative direction
ƒ
Negative hardware limit switch is active
W Retracting in positive direction
4. Only with user software
£1.x (A−SW see nameplate):
Activate limit switch monitoring: Set Ctrl1.Bit1 = 0 (FALSE).