Commissioning – Lenze ECSCMxxx User Manual
Page 147

Commissioning
Setting of homing parameters
Homing modes
l
147
EDBCSXM064 EN 11.0
Modes 4 and 5
Approaching the reference switch, reversing, and travelling to the zero pulse (zero position
of the position encoder).
Ref
1
5
3
R
2
4
6
0
ECSXA512
Fig. 6−18
Homing in mode 4
0 Negative hardware limit switch
1 Zero pulse (zero position of the position encoder)
2 Reference switch
3 Positive hardware limit switch
4 Load (e. g. slide)
5 Direction of travel
6 Home position
The load (e.g. slide) travels from its original position to the reference switch. At the
approached reference switch the direction of travel is reversed and the load travels to the
first zero pulse after leaving the reference switch. The zero pulse bears the home position.
If the drive is already situated at the reference switch, the direction of travel is reversed
immediately.
Settings
Mode 4
(Homing towards the positive hardware limit switch)
Mode 5
(Homing towards the negative hardware limit switch)
l
Set C3010 = 4.
l
Set C3010 = 5.
)
Note!
ƒ
Single−turn absolute value encoder (SinCos encoder) and resolver do not
have a zero pulse. Here the zero position corresponds to the zero pulse
.
ƒ
In case of multi−turn absolute value encoders, only the homing modes
6 ... 11 and 99 can be used (C3010 = 6 ... 11 or 99).
ƒ
If the digital frequency output (X8) is to be used as encoder simulation with
zero pulse, set C0540=2.