Commissioning

Commissioning steps (overview)

Setting of homing

6

l

99

EDBCSXM064 EN 11.0

Detailed

information

Brief description

Settings

7.

A Select "Interpolated

Position Mode".

The "Interpolated Position Mode" is automatically selected
by the higher−level control (PLC): C5000 = 7
The operating mode can also be set manually in the GDC
parameter menu under Motion

W Operating mode.

^ 161

B Confirm setting of

"Interpolated Position
Mode".

In order that the drive performs a travel according to the
setpoint selection, the ECSxM axis module must write the
value from C5000 into C5001 (here C5001 = 7).
If this is not the case, set the operating mode manually in the
GDC parameter menu under Motion

W Operating mode.

8.

Start travel according to the
setpoint selection.

The master control (PLC) set the control word bit
Ctrl1.Bit12 = 1 (TRUE).
Note:
In order to interrupt homing, reset the Ctrl1.Bit12 to "0"
using the master control.

^ 131

The settings for homing are now completed.

Proceed as follows:

ƒ

Save parameter set with GDC in the parameter set file.

ƒ

Optimise drive behaviour (

^ 183).