Configuration – Lenze ECSCMxxx User Manual
Page 200

Configuration
Configuring MotionBus/system bus (CAN)
Setting CAN node address and baud rate
l
200
EDBCSXM064 EN 11.0
8.1.1.2
Settings via codes
)
Note!
ƒ
The settings in C0350 (CAN node address) and C0351 (baud rate) are only
used if the (address) switches 2 ... 7 of the DIP switch S1 are switched off
(OFF).
ƒ
If only one (address) switch 2 ... 7 is switched on (ON), the settings of the DIP
switch S1 usually apply.
ƒ
The baud rate (C0351) must be set identically for all CAN bus nodes.
ƒ
If the Lenze setting has been loaded via C0002,
– C0351 is set to 0 (500 kbit/s);
– you have to reset the baud rate (C0351) and the CAN node address
(C0350).
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0350 CAN address
32
Node address for CAN bus
interface X4
l
This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
(
^ 197)
l
After the setting process, a
reset node is required.
l
A definite node address must
be assigned to each CAN
node.
^ 197
^ 351
1
{1}
63
C0351 CAN baud rate
0
{4}
Baud rate for CAN bus interface
X4
l
The baud rate must be set
identically for all CAN nodes.
l
This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
l
After the setting process, a
reset node is required.
l
When the Lenze setting is
loaded via C0002, C0351 is
set to 0 (500 kbit/s).
^ 197
0
500 kbps
1
250 kbits/sec
2
125 kbit/s
3
50 kbps
4
1000 kbit/s
Save changes with C0003 = 1.
The settings are only accepted after carrying out one of the following actions:
ƒ
Renewed switch−on of the 24 V low−voltage supply
ƒ
Reset node via the bus system (by the network management (NMT))
ƒ
Reset node with C0358 = 1
)
Note!
If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).