Appendix – Lenze ECSCMxxx User Manual
Page 308

Appendix
Code table
l
308
EDBCSXM064 EN 11.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0605 MONIT OH5
2
Fault response − monitoring of
temperature inside the
controller.
Temperature threshold can be
set under C0124.
^ 232
0
TRIP
2
Warning
3
Off
C0606 MONIT OC8
2
Fault response − monitoring of
I
2
x t motor utilisation.
Threshold can be set under
C0120.
^ 237
0
TRIP
2
Warning
3
Off
C0607 MONIT NMAX
0
Fault response − maximum speed
monitoring of the machine
0
TRIP
2
Warning
3
Off
C0608 ovr. Tx−Queue
2
Fault response − transmission
memory overflow of free CAN
objects
0
TRIP
1
Message
2
Warning
3
Off
4
FAIL−QSP
C0609 ovr. Rx−Isr
0
Fault response Receive memory
overflow of free CAN objects
0
TRIP
4
FAIL−QSP
C0651 Delay T
0.006
{1.000}
DT1−1 time constant
−0.005
{0.001 s}
199.999
C0653 Sensibility
1
DT1−1 sensitivity
1
15 bits
2
14 Bit
3
13 bits
4
12 bits
5
11 bits
6
10 bits
7
9 bits
C0855
Digital process data input words
are indicated on the AIF interface
(AIF1_IN)
Hexadecimal value is bit−coded.
Read only
1 AIF1 IN bits
0000
{hex}
FFFF Input word 2 (bit 0 ... 15)
2 AIF1 IN bits
Input word 3 (bit 0 ... 15)