Monitoring functions, Overview of monitoring functions – Lenze ECSCMxxx User Manual
Page 223

Monitoring
functions
Overview of monitoring functions
9
l
223
EDBCSXM064
EN 11.0
Possible fault responses
l Lenze setting
ü Can be set
Monitoring
Off
Fail−QSP
Warning
Message
TRIP
Code
Source
Description
Fault message
x085
Sd5
Master current value encoder error on analog input X6/AI+, AI− (C0034 = 1)
MCTRL
C0598
ь
ь
l
x087
Sd7
Absolute value encoder initialisation error at X8
MCTRL
l
x088
Sd8
Sin&cos signal fault at X8
MCTRL
C0580
ü
l
x089
PL
Fault during rotor position adjustment
MCTRL
l
Speed
x190
nErr
Speed control error (monitoring window C0576)
MCTRL
C0579
ь
ь
ь
ь
l
x200
NMAX
Max. system speed (C0596) has been exceeded.
MCTRL
C0607
l
ь
ь
Float error
0209
float Sys−T
Float error in system task (ID 0)
Internal
l
ь
ь
2)
0210
float Cycl.−T Float error in cyclic task (PLC_PRG ID 1)
Internal
l
ь
ь
2)
0211
float Task1
Float error in task 1 (ID 2)
Internal
l
ь
ь
2)
...
...
...
0218
float Task8
Float error in task 8 (ID 9)
Time−out / overflow
0105
H05
Internal fault (memory)
Internal
l
x108
H08
Extension board not connected properly or not supported by program.
Internal
l
0201
overrun
Task1
Time−out in task 1 (ID 2)
Internal
l
ь
ь
2)
...
...
...
0208
overrun
Task8
Time−out in task 8 (ID 9)
0219
overrun
Cycl.−T
Time−out in cyclic task (PLC_PRG, ID 1)
Internal
l
ь
ь
2)
0220
noT−Fkt
Credit
Not enough technology units available in the PLC.
Internal
l
0230
No program No PLC program loaded in the PLC.
Internal
l
0231
Unallowed
Lib
You have called the library function in the PLC program. This function is not
supported.
Internal
l
x232
NoCamData Motion profiles (cam data) are not available.
Internal
l
x240
ovrTrans
Queue
Overflow of transmit request memory
Free CAN
objects
C0608
l
ь
ь
ь
ь
x241
ovr Receive
Too many receive telegrams
Free CAN
objects
C0609
l
ü
Parameter setting
x: 0 = TRIP, 1 = message, 2 = warning, 3 = FAIL−QSP
1)
Adjustable in the DDS under Project
W Exceptional handling
2)
For ECSxA... only