Monitoring functions
Configuring monitoring functions
DC−bus voltage monitoring (OU, LU)
l
243
EDBCSXM064 EN 11.0
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0173 UG limit
11
Adaptation of the DC−bus
voltage thresholds:
l
Check during commissioning
and adapt, if necessary.
l
All drive components in DC
bus connections must have
the same thresholds.
– LU = Undervoltage
threshold
– OU = Overvoltage threshold
^ 101
0
Mains = 230 V
± B
Operation on 230 V mains with
or without brake unit
LU = 130 V, OU = 400 V
1
Mains = 400 V
± B
Operation on 400 V mains with
or without brake unit
LU = 285 V, OU = 800 V
2
Mains = 460 V
± B
Operation on 460 V mains with
or without brake unit
LU = 328 V, OU = 800 V
3
Mains = 480V − B
Operation on 480 V mains
without brake unit
LU = 342 V, OU = 800 V
4
Mains = 480V + B
Operation on 480 V mains with
brake unit
LU = 342 V, OU = 800 V
10
Mains = 230 V
± B
Operation on 230 V mains with
or without brake unit
LU = C0174, OU = 400 V
11
Mains = 400 V
± B
Operation on 400 V mains with
or without brake unit
LU = C0174, OU = 800 V
12
Mains = 460 V
± B
Operation on 460 V mains with
or without brake unit
LU = C0174, OU = 800 V
13
Mains = 480V − B
Operation on 480 V mains
without brake unit
LU = C0174, OU = 800 V
14
Mains = 480V + B
Operation on 480 V mains with
brake unit
LU = C0174, OU = 800 V
C0174 UG min
60
Undervoltage threshold of DC
bus (LU)
^ 101
15
{1 V}
342