Holding brake configuration
l
106
EDBCSXM064 EN 11.0
Code
Name
Description
C0195
Brake closing
time/engagement
time
The time required for closing the holding brake.
l
When Ctrl1.Bit7 = 0 (FALSE), the brake is closed.
l
Only after this time has elapsed, the controller inhibit is activated.
C0196
Brake opening
time/disengagement
time
The time required for opening the holding brake.
l
During the time set the drive generates the torque set under C0244
against the holding brake.
l
If an actual speed higher than the value in C0472/10 is detected before the
brake opening time (C0196) has expired, the drive can immediately change
to speed−controlled operation.
C0244
Holding torque
Holding torque of the drive against the holding brake
l
100 %
¢ value of C0057
C0472/10 FCODE analog [%]
Speed threshold for closing the brake:
l
Only if the actual speed value has fallen below the speed threshold, the
"close brake" signal is output.
l
This code refers to the maximum speed set in C0011.
Note: Enter a value > 0 so that the brake can be opened.
C0472/11 FCODE analog [%]
Value/direction of the torque against the holding brake.
C0118
Polarity of the digital
outputs
In the Lenze setting, the outputs are "HIGH level active" (
^ 142).
l
C0118/1: Output X6/DO1 (DIGOUT_bOut1_b)
l
C0118/2: Output X25 (DIGOUT_bRelais_b, brake connection)
C0602
Fault response − open
circuit monitoring at
X25
Fault response to open circuit monitoring of relay output X25
l
0: TRIP
l
2: Message
l
3: Off (Lenze setting)
l
4: FAIL−QSP