Appendix – Lenze ECSCMxxx User Manual
Page 299

Appendix
Code table
l
299
EDBCSXM064 EN 11.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0371 Gateway Ch.
1
Selection of the gateway channel
^ 217
0
CAN
Use CAN bus interface X4
1
CAN−AUX
Use CAN bus interface X14
C0381 HeartProdTim
e
0
Heartbeat (slave):
HeartbeatProducerTime
l
Time interval for sending the
heartbeat message
l
Only relevant for setting
C0352 = 3.
0
{1 ms}
65535
C0382 GuardTime
0
Node Guarding (slave):
NodeGuardTime
l
Time interval of the status
inquiry of the master
l
Only relevant for setting
C0352 = 4.
^ 212
0
{1 ms}
65535
C0383 LifeTimeFact
0
Node Guarding (slave):
NodeLifeTime factor
l
Factor for the monitoring
time of NodeLifeTime
l
NodeLifeTime = C0383 x
C0382 (NodeGuardTime)
l
Only relevant for setting
C0352 = 4.
^ 212
0
{1}
255
C0384 Err
NodeGuard
3
Node Guarding (slave)
l
Response for the occurrence
of a NodeGuard−Event
l
Only relevant for setting
C0352 = 4.
^ 212
0
TRIP
1
Message
2
Warning
3
Off
4
FAIL−QSP
C0400 DIS: AnalogIn
Signal at the analog input
Read only
−199.99
{0.01 %}
199.99
C0414 DIS: ResQual.
Resolver modulation
Quality of the resolver excitation
amplitude set under C0416
(recommendation: 0.5 ... 1.2;
ideal 1.0)
^ 110
0.00
{0.01}
1,60