13 setting of homing parameters, 1 homing parameters, Homing parameters – Lenze ECSCMxxx User Manual
Page 143: Commissioning

Commissioning
Setting of homing parameters
Homing parameters
l
143
EDBCSXM064 EN 11.0
6.13
Setting of homing parameters
During homing the drive traverses in a preselected mode (C3010). While doing so, the zero
position (reference) is detected by means of a reference mark and transmitted to the drive
control. All position data refer to this reference.
The GDC parameter menu includes the codes for setting the homing parameters (e.g.
homing mode, speed, offsets) under Motion
W Homing.
ECSXA537
Fig. 6−15
GDC view: Short setup, entry of homing parameters
6.13.1
Homing parameters
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0935 L_REF1 speed
100
Traversing speed of homing
^ 143
1
{1 rpm}
16000
C0936 L_REF1 Ti
1.0
Deceleration time (T
i
) of homing
^ 143
0.01
{0.01 s}
650.00
C3008 HomeMlim
10.0
Torque limit value for homing
mode C3010 = 16 or 17
(100.00 % = maximum torque
from C0057)
^ 153
0.00
{0.01 %}
100.00
C3009 TimeHome
Mlim
100
Duration for detecting the
mechanical limit stop for homing
mode C3010 = 16 or 17
^ 153
0
{1 ms}
65535