Appendix – Lenze ECSCMxxx User Manual
Page 292

Appendix
Code table
l
292
EDBCSXM064 EN 11.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0173 UG limit
11
Adaptation of the DC−bus
voltage thresholds:
l
Check during commissioning
and adapt, if necessary.
l
All drive components in DC
bus connections must have
the same thresholds.
– LU = Undervoltage
threshold
– OU = Overvoltage threshold
^ 101
0
Mains = 230 V
± B
Operation on 230 V mains with
or without brake unit
LU = 130 V, OU = 400 V
1
Mains = 400 V
± B
Operation on 400 V mains with
or without brake unit
LU = 285 V, OU = 800 V
2
Mains = 460 V
± B
Operation on 460 V mains with
or without brake unit
LU = 328 V, OU = 800 V
3
Mains = 480V − B
Operation on 480 V mains
without brake unit
LU = 342 V, OU = 800 V
4
Mains = 480V + B
Operation on 480 V mains with
brake unit
LU = 342 V, OU = 800 V
10
Mains = 230 V
± B
Operation on 230 V mains with
or without brake unit
LU = C0174, OU = 400 V
11
Mains = 400 V
± B
Operation on 400 V mains with
or without brake unit
LU = C0174, OU = 800 V
12
Mains = 460 V
± B
Operation on 460 V mains with
or without brake unit
LU = C0174, OU = 800 V
13
Mains = 480V − B
Operation on 480 V mains
without brake unit
LU = C0174, OU = 800 V
14
Mains = 480V + B
Operation on 480 V mains with
brake unit
LU = C0174, OU = 800 V
C0174 UG min
60
Undervoltage threshold of DC
bus (LU)
^ 101
15
{1 V}
342
C0175 UG−Relais Fkt
1
Charge relay behaviour with
undervoltage (LU) in the DC bus.
^ 101
1
Standard
Relay switches as a function of
LU.
2
One Time
Relay switches when LU is
exceeded for the first time and
remains on.
3
Fixed On
Charging current limitation is
inactive.
l
Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.
l
Setting for operation with
ECSxE power supply module.