Monitoring functions – Lenze ECSCMxxx User Manual
Page 242

Monitoring functions
Configuring monitoring functions
DC−bus voltage monitoring (OU, LU)
l
242
EDBCSXM064 EN 11.0
Selection
Mains voltage
Brake unit
LU message
(Undervoltage)
OU message
(Overvoltage)
C0173
Power supply module
[V AC]
Setting
[V DC]
Resetting
[V DC]
Setting
[V DC]
Resetting
[V DC]
0
230
yes/no
130
275
400
390
1
400
yes/no
285
430
800
790
2
400 ... 460
yes/no
328
473
800
790
3
480
no
342
487
800
785
4
480
yes
342
487
800
785
10
230
yes/no
C0174
C0174 + 5 V
400
390
11
400 (Lenze setting)
yes/no
C0174
C0174 + 5 V
800
790
12
400 ... 460
yes/no
C0174
C0174 + 5 V
800
790
13
480
no
C0174
C0174 + 5 V
800
785
14
480
yes
C0174
C0174 + 5 V
800
785
I
Tip!
If undervoltage is existent for more that 3 s, or if mains connection is carried
out, an entry into the fault memory is effected.
ƒ
This operational mode can occur if the control module is fed via the
terminals X6/+24 and X6/GND by means of an external supply and the
mains are disconnected.
ƒ
If there is no undervoltage anymore (mains are reconnected again), the
entry in the fault memory is not continued, but deleted. This case does not
describe an error, but a state of the drive controller.
Undervoltages of less than 3 s are interpreted as a fault (e. g. mains fault) and
are entered into the fault memory. In this case, the fault memory is updated.