Troubleshooting and fault elimination, Fault messages causes and remedies – Lenze ECSCMxxx User Manual
Page 271

Troubleshooting and fault elimination
Fault messages
Causes and remedies
l
271
EDBCSXM064 EN 11.0
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
0050
OH
Heatsink temperature > +90
°C
Ambient temperature
T
u
> +40
°C or > +50 °C
l
Allow module to cool and
ensure better ventilation.
l
Check ambient temperature in
the control cabinet.
Heatsink is very dirty.
Clean heatsink.
Wrong mounting position
Change mounting position.
0051
OH1
Interior temperature > +90
°C
Ambient temperature
T
u
> +40
°C or > +50 °C
l
Allow module to cool and
ensure better ventilation.
l
Check ambient temperature in
the control cabinet.
Wrong mounting position
Change mounting position.
x053
OH3
Motor temperature
> +150
°C threshold
(temperature detection via
resolver or incremental value
encoder)
Motor is thermally overloaded
due to:
l
Impermissible continuous
current
l
Frequent or too long
acceleration processes
l
Check drive dimensioning.
l
Switch off monitoring
(C0583 = 3).
No PTC/temperature contact
connected.
Correct wiring.
x054
OH4
Heatsink temperature > C0122
Ambient temperature T
u
> +40
°C
or > +50
°C
l
Allow module to cool and
ensure better ventilation.
l
Check ambient temperature in
the control cabinet.
l
Switch off monitoring
(C0582 = 3).
Heatsink is very dirty.
Clean heatsink
Wrong mounting position
Change mounting position.
The value specified under C0122
is set too low.
Enter a higher value under C0122.
x055
OH5
Interior temperature > C0124
l
Allow module to cool and
ensure better ventilation.
l
Check ambient temperature in
the control cabinet.
l
Switch off monitoring
(C0605 = 3).
The value under C0124 is set too
low.
Enter a higher value under C0124.
x057
OH7
Motor temperature > C0121
(temperature detection via
resolver or incremental value
encoder)
Motor is thermally overloaded
due to:
l
Impermissible continuous
current
l
Frequent or too long
acceleration processes
l
Check drive dimensioning.
l
Switch off monitoring
(C0584 = 3).
No PTC/temperature contact
connected.
Correct wiring.
The value specified under C0121
is set too low.
Enter a higher value in C0121.
x058
OH8
Motor temperature via inputs T1
and T2 is too high.
Motor is thermally overloaded
due to:
l
Impermissible continuous
current
l
Frequent or too long
acceleration processes
l
Check drive dimensioning.
l
Switch off monitoring
(C0585 = 3).
Terminals T1 and T2 are not
connected
Connect PTC/temperature
contact.
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP