15 controller enable (cinh = 0), Commissioning – Lenze ECSCMxxx User Manual
Page 169

Commissioning
Controller enable (CINH = 0)
l
169
EDBCSXM064 EN 11.0
6.15
Controller enable (CINH = 0)
The controller will only be enabled internally if no signal sources relevant for the controller
inhibit (CINH) are activated (i.e. CINH−signal sources = 0).
The following table shows the conditions for controller enable:
Source of the
Controller inhibit
Controller
inhibit
Controller
enable
Note
Terminal X6/SI1
0 ... +4 V
(LOW level)
+13 ... +30 V
(HIGH level)
For controller enable, X6/SI1 must be
= HIGH and X6/SI2 must be = HIGH.
Terminal X6/SI2
0 ... +4 V
(LOW level)
+13 ... +30 V
(HIGH level)
C0040
C0040 = 0
C0040 = 1
Operating
module/keypad
s key
u key
Inhibiting with
s key is only possible if
the
s key is assigned with "CINH" via
C0469.
Fault
l
In case of TRIP
l
In case of
message
No fault active
For check see
^ 263.
Control word
l
MotionBus
(
^ 131)
C3153/Bit 9 = 1
C3153/Bit 9 = 0
GDC function key:
l
Note: With ECS−M, the controller is enabled
via the master control!
l
C4040
C4040/Bit 9 = 1
C4040/Bit 9 = 0
Fieldbus module
See operating instructions for the respective fieldbus module.
LED status displays
LED
Operating state
Red
Green
Off
On
Enable through master control
l
X6/SI1 = HIGH
l
X6/SI2 = HIGH
Off
Blinking
No enable through master control
l
X6/SI1 = HIGH
l
X6/SI2 = HIGH
)
Note!
All signal sources act like a series connection of switches which are
independent of each other.