Commissioning
Configuring the digital inputs and outputs
Digital inputs for communication via the MotionBus (CAN) X4
l
141
EDBCSXM064 EN 11.0
6.12.1
Digital inputs for communication via the MotionBus (CAN) X4
Setting C4011 = 0:
Terminal
Function
Level
Response
X6/DI1
Quick stop (QSP)
LOW
The drive is decelerated to standstill within the deceleration
time set in C0105.
HIGH
The motor follows the setpoint selection.
X6/DI2
Reference switch/
Touch probe sensor
LOW
No response
HIGH
Activation of reference switch/touch probe sensor (both edge
active)
X6/DI3
Positive hardware limit
switch
LOW
The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.
HIGH
No response
X6/DI4
Negative hardware limit
switch
LOW
The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.
HIGH
No response
6.12.2
Digital inputs for communication via the automation interface (AIF) X1
Setting C4011 = 1:
Terminal
Function
Level
Response
X6/DI1
Sync source
LOW
No sync
HIGH
Sync is active
X6/DI2
Reference switch/
Touch probe sensor
LOW
No response
HIGH
Activation of reference switch/touch probe sensor (both edge
active)
X6/DI3
Positive hardware limit
switch
LOW
The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.
HIGH
No response
X6/DI4
Negative hardware limit
switch
LOW
The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.
HIGH
No response