Commissioning

Setting of the feedback system for position and speed control
Absolute value encoder as position encoder and resolver as speed encoder

6

l

126

EDBCSXM064 EN 11.0

6.7.6

Absolute value encoder as position encoder and resolver as speed encoder

}

Danger!

Valid when using an operating software up to and including V7.0:
When absolute value encoders are used, uncontrolled movements of the drive
are possible!
If an absolute value encoder is disconnected from the axis module during
operation, the fault OH3−TRIP occurs. If the absolute value encoder now is
connected to X8 again and a TRIP−RESET is carried out, the drive may start up in
an uncontrolled manner with a high speed and a high torque. A SD8−TRIP will
not occur, as would be expected.
Possible consequences:

ƒ

Death or severe injuries

ƒ

Destruction or damage of the machine/drive

Protective measures:

ƒ

If a fault (trip) occurs during commissioning when an absolute value
encoder is used, check the history buffer C0168. If an Sd8−TRIP is at the
second or third place, a reinitialisation is absolutely necessary. For this
purpose, switch off and on again the 24−V supply of the control electronics.

An absolute value encoder Hiperface® interface connected to X8 can be configured as a
position encoder with a resolver connected to X7 being used as a speed encoder.

Observe the following setting sequence:

1. Select absolute value encoder as position encoder.

– Single−turn encoder: C0490 = 3
– Multi−turn encoder: C0490 = 4

2. Select resolver as speed encoder.

– C0495 = 0

3. Select an absolute value encoder.

– Single−turn encoder: C0419 = 307 ... 311
– Multi−turn encoder: C0419 = 407 ... 411
The encoder data (C0420, C0421, C0427) is set automatically in accordance with the
selection.