Commissioning

Holding brake configuration

6

l

105

EDBCSXM064 EN 11.0

6.6

Holding brake configuration

I

Tip!

If you use a motor without a holding brake, you can skip this chapter.

In the GDC, the parameters or codes to be set can be found in the parameter menu under
Short setup

W Brake.

ECSXA531

Fig. 6−7

GDC view: Short setup of the holding brake

)

Note!

The codes C0195, C0196, C0244, C0472/10 and C0472/11 are only effective if
the brake logic is active (C4020 = 1).

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C4020 Brake logic

1

Activate brake logic

^ 105

0

Brake Off

1

Brake On

2

Brake control via application control
word bit 2

Brake control via control bit 2 in
the application control word:

l

0: brake closed (relay output
is not triggered)

l

1: brake open (relay output is
triggered )