beautypg.com

F4 modbus applications: autostart step – Watlow Series F4S/D User Manual

Page 95

background image

Wa t l o w S e r i e s F 4 S / D

C o m m u n i c a t i o n s

7 . 1 9

F4 Modbus Applications: Autostart Step

Set Step Type to

"Autostart"

Write Modbus Register

4003=0

Enter Month to Start Profile

Write Modbus Register

4005=1 to 12

Enter Day to Start Profile

Write Modbus Register

4006=1 to 31

Start on a

Date or

Day?

Date

Enter Day of week

Write Modbus Register

4008=0 to 7

Day

Enter Year to Start Profile

Write Modbus Register

4007=1998 to 2035

0 =

Every Day

1 =

Sunday

2 =

Monday

3 =

Tuesday

4 =

Wednesday

5 =

Thursday

6 =

Friday

7 =

Saturday

Set "Day" Flag

Write Modbus Register

4004=1

Set "Date" Flag

Write Modbus Register

4004=0

Save Changes

Write Modbus Register

25=0

1 =

Jan
.
.
.

12 =

Dec

Done

Enter Hour

Write Modbus Register

4009=0 to 23

Enter Minute

Write Modbus Register

4010=0 to 59

Enter Second

Write Modbus Register

4011=0 to 59

24 Hour

Clock

Format

Autostart pauses a profile until the specified date or day, and time (of a 24-hour-

clock).