Calibration menu map, Retransmit 2 setup and calibration – Watlow Series F4S/D User Manual
Page 112

9 . 6
■
C a l i b r a t i o n
Wa t l o w S e r i e s F 4 S / D
<
to adjust the display to the reading on the
volt/ammeter. The controller should stabilize
within one second. Repeat until the volt/amme-
ter reads 4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate
Rexmit 1 prompt. At the 20.000mA prompt
press . once. Use the Up Key > or the Down
Key < to adjust the display to the reading on
the volt/ammeter. The controller should stabi-
lize within one second. Repeat until the
volt/ammeter reads 20.000mA. Press . to
store the value.
Volts
5. Connect the volt/ammeter to terminals 48 (+)
and 49 (-).
6. Press the Right Key . at the Calibrate
Rexmit 1 prompt. At the 1.000V prompt press
.
once. Use the Up Key > or the Down Key
<
to adjust the display to the reading on the
volt/ammeter. The controller should stabilize
within one second. Repeat until the volt/amme-
ter reads 1.000V. Press . to store the value.
7. Press the Right Key . at the Calibrate
Rexmit 1 prompt. At the 10.000V prompt press
.
once. Use the Up Key > or the Down Key
<
to adjust the display to the reading on the
volt/ammeter. The controller should stabilize
within one second. Repeat until the volt/amme-
ter reads 10.000V. Press . to store the value.
8. Rewire for operation and verify calibration.
Retransmit 2 Setup and Calibration
1. Connect the correct power supply to terminals
1, 2 and 3 (see the Wiring Chapter and the
Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 47 (+)
and 46 (-).
3. Press the Right Key . at the Calibrate
Rexmit 2 prompt. At the 4.000mA prompt press
.
once. Use the Up Key > or the Down Key
<
to adjust the display to the reading on the
volt/ammeter. The controller should stabilize
within one second. Repeat until the volt/amme-
ter reads 4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate
Rexmit 2 prompt. At the 20.000mA prompt
press . once. Use the Up Key > or the Down
Key < to adjust the display to the reading on
the volt/ammeter. The controller should stabi-
lize within one second. Repeat until the
volt/ammeter reads 20.000mA. Press . to
store the value.
Volts
5. Connect the volt/ammeter to terminals 45 (+)
and 46 (-).
6. Press the Right Key . at the Calibrate
Rexmit 2 prompt. At the 1.000V prompt press
.
once. Use the Up Key > or the Down Key
<
to adjust the display to the reading on the
volt/ammeter. The controller should stabilize
within one second. Repeat until the volt/amme-
ter reads 1.000V. Press . to store the value.
7. Press the Right Key . at the Calibrate
Rexmit 2 prompt. At the 10.000V prompt press
.
once. Use the Up Key > or the Down Key
Calibration Menu Map
Calibrate Input 1
Calibrate Input 2
Calibrate Input 3
Calibrate Output 1A
Calibrate Output 1B
Calibrate Output 2A
Calibrate Output 2B
Calibrate Rexmit 1
Calibrate Rexmit 2
Restore In1 Cal
Restore In2 Cal
Restore In3 Cal