Watlow Series F4S/D User Manual
Page 81
Wa t l o w S e r i e s F 4 S / D
C o m m u n i c a t i o n s
■
7 . 5
1077
Digital Input 2, Start Profile
r/w
1 to 40
1078
Digital Input 2, Start Step
r/w
1 to 256
225
Digital Input 3, Status
0
Low
1
High
1065
Digital Input 3 Condition
r/w
0
Low
1
High
1064
Digital Input 3 Function
r/w
0
Off
1
Panel Lock
2
Reset Alarm
3
Control Outputs Off
4
All Outputs Off
5
Digital Outputs Off
6
Start Profile
7
Pause Profile
8
Resume Profile
9
Terminate Profile
10 Wait For Event
1079
Digital Input 3, Start Profile
r/w
1 to 40
1080
Digital Input 3, Start Step
r/w
1 to 256
237
Digital Input 4, Status
0
Low
1
High
1067
Digital Input 4 Condition
r/w
0
Low
1
High
1066
Digital Input 4 Function
r/w
0
Off
1
Panel Lock
2
Reset Alarm
3
Control Outputs Off
4
All Outputs Off
5
Digital Outputs Off
6
Start Profile
7
Pause Profile
8
Resume Profile
9
Terminate Profile
10 Wait For Event
1081
Digital Input 4, Start Profile
r/w
1 to 40
1082
Digital Input 4, Start Step
r/w
1 to 256
2000
Digital Output 1, Condition
r/w
0
Off
1
On
2001
Digital Output 1 Function
r/w
0
Off
1
Event Output
2010
Digital Output 2, Condition
r/w
0
Off
1
On
2011
Digital Output 2 Function
r/w
0
Off
1
Event Output
2020
Digital Output 3, Condition
r/w
0
Off
1
On
2021
Digital Output 3 Function
r/w
0
Off
1
Event Output
2030
Digital Output 4, Condition
r/w
0
Off
1
On
2031
Digital Output 4 Function
r/w
0
Off
1
Event Output
2040
Digital Output 5, Condition
r/w
0
Off
1
On
2041
Digital Output 5 Function
r/w
0
Off
1
Event Output
2
Complementary Output
2946
Control Output
r/w
0
1A
1
1B
2
2A
3
2B
2050
Digital Output 6, Condition
r/w
0
Off
1
On
2051
Digital Output 6 Function
r/w
0
Off
1
Event Output
3
Boost Heat
2060
Digital Output 7, Condition
r/w
0
Off
1
On
2061
Digital Output 7 Function
r/w
0
Off
1
Event Output
4
Boost Cool
2070
Digital Output 8, Condition
r/w
0
Off
1
On
2071
Digital Output 8 Function
r/w
0
Off
1
Event Output
5
Compressor
2072
Power On
r/w
Value
2073
Power Off
r/w
Value
2074
Delay On
r/w
Value
2055
Delay Off
r/w
Value
1513
Display Test, Test
w
0
Off
1
On
1307
Edit PID, Lockout
r/w
0
Full Access
1
Read Only
2
Password
3
Hidden
607
Error Latching, Analog Input 1
r/w
0
Self Clear
1
Latch
617
Error Latching, Analog Input 2
r/w
0
Self Clear
1
Latch
627
Error Latching, Analog Input 3
r/w
0
Self Clear
1
Latch
1303
Factory Page, Lockout
r/w
0
Full Access
1
Read Only
2
Password
604
Filter Time, Analog Input 1
r/w
-600 to 600
(expressed in tenths of seconds)
614
Filter Time, Analog Input 2
r/w
-600 to 600
(expressed in tenths of seconds)
624
Filter Time, Analog Input 3
r/w
-600 to 600
(expressed in tenths of seconds)
1602
Full Defaults
800 yes
1205
Guaranteed Soak Band, Channel 1
r/w
1 to 9999
1212
Guaranteed Soak Band, Channel 2
r/w
1 to 9999
1220
Guaranteed Soak Band 1 Source
r/w
0
Input 1
1 Input
2
2
Input 3
1221
Guaranteed Soak Band 2 Source
r/w
0
Input 1
1
Input 2
2
Input 3
714
High Power Limit, Control Output 1A
r/w
Low Limit+1 to 100
(expressed in %)
731
High Power Limit, Control Output 1B
r/w
Low Limit+1 to 100
(expressed in %)
✔ NOTE:
For more information
about parameters, see
the Index.