Wa t l o w S e r i e s F 4 S / D

C o m m u n i c a t i o n s

7 . 7

2651

Integral 1B , Cascade PID Set 1, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

2661

Integral 1B , Cascade PID Set 2, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

2671

Integral 1B , Cascade PID Set 3, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

2681

Integral 1B , Cascade PID Set 4, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

2691

Integral 1B , Cascade PID Set 5, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

551

Integral 1B, PID Set 1, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

561

Integral 1B, PID Set 2, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

571

Integral 1B, PID Set 3, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

581

Integral 1B, PID Set 4, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

591

Integral 1B, PID Set 5, Channel 1

r/w

000 to 9999

(expressed in hundredths of minutes)

2501

Integral 2A, PID Set 6, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2511

Integral 2A, PID Set 7, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2521

Integral 2A, PID Set 8, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2531

Integral 2A, PID Set 9, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2541

Integral 2A, PID Set 10, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2551

Integral 2B, PID Set 6, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2561

Integral 2B, PID Set 7, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2571

Integral 2B, PID Set 8, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2581

Integral 2B, PID Set 9, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

2591

Integral 2B, PID Set 10, Channel 2

r/w

000 to 9999

(expressed in hundredths of minutes)

1515

Line Frequency, Diagnostics

r

xx

715

Low Power Limit, Control Output 1A

r/w

0 to High Limit-1000 to 9999

(expressed in %)

732

Low Power Limit, Control Output 1B

r/w

0 to High Limit-1

(expressed in %)

749

Low Power Limit, Control Output 2A

r/w

0 to High Limit-1

(expressed in %)

766

Low Power Limit, Control Output 2B

r/w

0 to High Limit-1

(expressed in %)

710

Low Scale, Retransmit Output 1

r/w

-19999 to Scale High-1

(minimum sensor range)

727

Low Scale, Retransmit Output 2

r/w

-19999 to Scale High-2

(minimum sensor range)

5

Mfg. Date, Diagnostics

r

xxxx

0

Model, Diagnostics

r

F4

3200-09 Name, Alarm 1 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3210-19 Name, Alarm 2 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3000-06 Name, Digital Input 1 (7 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3010-16 Name, Digital Input 2 (7 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3020-26 Name, Digital Input 3 (7 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3030-36 Name, Digital Input 4 (7 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3100-09 Name, Digital Output 1 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3110-19 Name, Digital Output 2 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3120-29 Name, Digital Output 3 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3130-39 Name, Digital Output 4 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3140-49 Name, Digital Output 5 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3150-59 Name, Digital Output 6 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3160-69 Name, Digital Output 7 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

3170-79 Name, Digital Output 8 (10 characters)
r/w

ASCII equivalent decimal code — see Modbus Naming Flowchart

904

Open Loop Channel 1

r/w

0

Off

1

On

907

Open Loop Channel 2

r/w

0

Off

1

On

200

Operation Mode, Status

r

0

Terminate Profile

1

Pre-run Profile

2

Running Profile

3

Holding Profile

16

Output 1A Type, Diagnostics

r

1

DC

2

SSR

3

Process

17

Output 1B Type, Diagnostics

r

0

None

1

DC

2

SSR

3

Process

18

Output 2A Type, Diagnostics

r

0

None

1

DC

2

SSR

3

Process

19

Output 2B Type, Diagnostics

r

0

None

1

DC

2

SSR

3

Process

900

PID Units, System

r/w

0

US (Reset/Rate)

1

SI (Integral/Derivative)

1206

Power-Out Action

r/w

0

Continue

1

Hold

2

Terminate

3

Reset

4

Idle Set Point 1

5

Idle Set Point 2

1213

Power-Out Time

r/w

0 to 9999 seconds

5500

Process Display

r/w

0

Input 1 only

1

Alternating

5501

Process Display, Input 1 Time

r/w

0 to 999

5502

Process Display, Input 2 Time

r/w

0 to 999

5503

Process Display, Input 3 Time

r/w

0 to 999

1606

Process Output 1A, 1.000V, Calibrate

w

0000 to 3000

(expressed in thousandths volts)

1607

Process Output 1A, 10.000V, Calibrate

w

0000 to 12000

(expressed in thousandths volts)

1605

Process Output 1A, 20.000mA, Calibrate

w

0000 to 24000

(expressed in microamps)

1604

Process Output 1A, 4.000mA, Calibrate

w

0000 to 6000

(expressed in microamps)

1611

Process Output 1B, 1.000V, Calibrate

w

0000 to 3000

(expressed in thousandths volts)

1612

Process Output 1B, 10.000V, Calibrate

w

0000 to 12000

(expressed in thousandths volts)

1610

Process Output 1B, 20.000mA, Calibrate

w

0000 to 24000

(expressed in microamps)

NOTE:
For more information

about parameters, see

the Index.