Profiles page parameter table, Event output, Analog input x (1 to 3) – Watlow Series F4S/D User Manual

Page 46

background image

4 . 1 4

P r o f i l e P r o g r a m m i n g

Wa t l o w S e r i e s F 4 S / D

Profiles Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

NOTE: Two sets of Modbus registers contain profile informa-
tion: In edit mode, the number of the profile being edited is at
4000, and the number of the step being edited is at 4001. When
the profile is running, the number of the profile being run is at
4100, and the number of the step being run is at 4101. All run
addresses are read only.

WARNING:

Check the configuration of the controller on the Setup Page be-
fore starting and running a profile (if the Setup Page is not
locked). Make sure settings are appropriate to the profile. If
the Setup Page is accessible, failure to check the configuration
before running a profile could result in damage to equipment
and/or property, and/or injury or death to personnel.

ç

Active if the associated Digital

Output is set to Event.

Output

4030 r/w [1]

4111

r

[1]

4031 r/w [2]

4112

r

[2]

4032 r/w [3]

4113

r

[3]

4033 r/w [4]

4114

r

[4]

4034 r/w [5]

4115

r

[5]

4035 r/w [6]

4116

r

[6]

4036 r/w [7]

4117

r

[7]

4037 r/w [8]

4118

r

[8]

Off (0)

Off (0)
On (1)

Output x (1 to 8)

Select this Digital

Output to be on or

off.

… > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > Event Output

Event Output

Active: Always.

Input

4022 r/w [1]

4024 r/w [2]

4026 r/w [3]

Follow input

selected

Range Low to Range

High

Enter Analog Input x

Select the process

value that will initi-

ate this step.

… > Ramp Time or Ramp Rate or Soak Step > Wait for: > To Wait for > Analog Input x (1 to 3)

Analog Input x (1 to 3)

Active if the selected Analog

Input is present (Analog Input

1 always is).

4021 r/w [1]

4108

r

[1]

4023 r/w [2]

4109

r

[2]

4025 r/w [3]

4110

r

[3]

Don’t Wait (0)

Don’t Wait (0)
Wait (1)

Analog Input x (1 to 3)

Select whether or

not to wait for a

process value to ini-

tiate this step.

Active if the selected Event Input

is Enabled.

Input

4013 r/w [1]

4104

r

[1]

4014 r/w [2]

4105

r

[2]

4015 r/w [3]

4106

r

[3]

4016 r/w [4]

4107 rw [4]

Don’t Wait (0)

Don’t Wait (0)
Wait for Off (1)
Wait for On (2)

Event Input x (1 to 4)

Select whether or

not to wait for a dig-

ital signal to initiate

this step.