Profiles Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
✔ NOTE: Two sets of Modbus registers contain profile informa-
tion: In edit mode, the number of the profile being edited is at
4000, and the number of the step being edited is at 4001. When
the profile is running, the number of the profile being run is at
4100, and the number of the step being run is at 4101. All run
addresses are read only.
WARNING:
Check the configuration of the controller on the Setup Page be-
fore starting and running a profile (if the Setup Page is not
locked). Make sure settings are appropriate to the profile. If
the Setup Page is accessible, failure to check the configuration
before running a profile could result in damage to equipment
and/or property, and/or injury or death to personnel.
ç
Active if the associated Digital
Output is set to Event.
Output
4030 r/w [1]
4111
r
[1]
4031 r/w [2]
4112
r
[2]
4032 r/w [3]
4113
r
[3]
4033 r/w [4]
4114
r
[4]
4034 r/w [5]
4115
r
[5]
4035 r/w [6]
4116
r
[6]
4036 r/w [7]
4117
r
[7]
4037 r/w [8]
4118
r
[8]
Off (0)
Off (0)
On (1)
Output x (1 to 8)
Select this Digital
Output to be on or
off.
… > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > Event Output
Event Output
Active: Always.
Input
4022 r/w [1]
4024 r/w [2]
4026 r/w [3]
Follow input
selected
Range Low to Range
High
Enter Analog Input x
Select the process
value that will initi-
ate this step.
… > Ramp Time or Ramp Rate or Soak Step > Wait for: > To Wait for > Analog Input x (1 to 3)
Analog Input x (1 to 3)
Active if the selected Analog
Input is present (Analog Input
1 always is).
4021 r/w [1]
4108
r
[1]
4023 r/w [2]
4109
r
[2]
4025 r/w [3]
4110
r
[3]
Don’t Wait (0)
Don’t Wait (0)
Wait (1)
Analog Input x (1 to 3)
Select whether or
not to wait for a
process value to ini-
tiate this step.
Active if the selected Event Input
is Enabled.
Input
4013 r/w [1]
4104
r
[1]
4014 r/w [2]
4105
r
[2]
4015 r/w [3]
4106
r
[3]
4016 r/w [4]
4107 rw [4]
Don’t Wait (0)
Don’t Wait (0)
Wait for Off (1)
Wait for On (2)
Event Input x (1 to 4)
Select whether or
not to wait for a dig-
ital signal to initiate
this step.