Setup page parameter table, Digital output x (1 to 8) – Watlow Series F4S/D User Manual
Page 61

Wa t l o w S e r i e s F 4 S / D
S e t u p
■
5 . 1 3
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set, Ch)
Parameters to Appear
✔ NOTE:
For more information about how parameter settings affect the con-
troller’s operation, see the Features Chapter.
ç
WARNING: Provide a labeled switch or circuit breaker near peripheral equipment per-
manently connected to the Series F4 digital outputs as the means of disconnection for
servicing. Failure to do so could result in damage to equipment and/or property,
and/or injury or death to personnel.
Active if Digital 6 or 7 Function
is set to Boost Heat or Boost
Cool.
Output
2054
[6]
2064
[7]
r/w
30 seconds
(30)
0 to 9999 seconds
(0 to 9999)
Boost Time Delay
Set time to delay
boost.
Active if Digital 6 or 7 Function
is set to Boost Heat or Boost
Cool.
Output
2052
[6]
2062
[7]
r/w
Heat 100%
(100)
Cool -100% (-
100)
0% to 100% for Heat
-100% to 0% for Cool
Boost Percent Power
Enable boost above
chosen power level.
Active: Always.
*Active if the selected output is not
Process.
**Operates based on Channel 1
power requirements.
2001
[1]
2011
[2]
2021
[3]
2031
[4]
2041
[5]
2051
[6]
2061
[7]
2071
[8]
r/w
Off (0)
Off (0)
Event Output (1)
Complementary Output
(Digital 5) (2)
*
Control Output 1A
*
Control Output 1B
*
Control Output 2A
*
Control Output 2B
**
Boost Heat (Digital 6)
(3)
**
Boost Cool (Digital 7)
(4)
**
Compressor (Digital
8) (5)
Function
Choose a function
for each digital out-
put.
Active: Always.
3100-3109
3110-3119
3120-3129
3130-3139
3140-3149
3150-3159
3160-3169
3170-3179
r/w
DIGIT OUTX
(ASCII Values)
Name
Name the digital
output for easy ref-
erence.
Main > Setup > Digital Output x (1 to 8)
Digital Output x (1 to 8)
Active: Always.
Output
712
[1]
729
[2]
r/w
0 (0)
-19999 to 30000
Range Low to Range
High
(-19999 to 30000)
Scale Offset
Shift the scale up
(+) or down (-) to
agree with source
signal.
Active: Always.
Output
711
[1]
728
[2]
r/w
High end of
sensor
range
Low Scale +1 to 30000
(maximum sensor
range) (Low Scale +1
to 30000)
High Scale
Set high end of cur-
rent or voltage
range to retransmit.