103

% Power Output 1A, Status

r

0 to 100

(expressed in %)

107

% Power Output 1B, Status

r

0 to 100

(expressed in %)

111

% Power Output 2A, Status

r

0 to 100

(expressed in %)

115

% Power Output 2B, Status

r

0 to 100

(expressed in %)

102

Alarm 1, Status

r
106

Alarm 2, Status

r
303

Alarm High Deviation, Alarm 1, Value

r/w

1 to 30000

322

Alarm High Deviation, Alarm 2, Value

r/w

1 to 30000

303

Alarm High Set Point, Alarm 1, Value

r/w

to Alarm 1 Low Set Point

322

Alarm High Set Point, Alarm 2, Value

r/w

to Alarm 2 Low Set Point

703

Alarm Hysteresis, Alarm Output 1

r/w

1 to 30000

720

Alarm Hysteresis, Alarm Output 2

r/w

1 to 30000

704

Alarm Latching, Alarm Output 1

r/w

0

Alarm Self-clears

1

Alarm Latches

721

Alarm Latching, Alarm Output 2

r/w

0

Alarm Self-clears

1

Alarm Latches

707

Alarm Logic, Alarm Output 1

r/w

0

Open on Alarm

1

Close on Alarm

724

Alarm Logic, Alarm Output 2

r/w

0

Open on Alarm

1

Close on Alarm

302

Alarm Low Deviation, Alarm 1, Value

r/w

-19999 to -1

321

Alarm Low Deviation, Alarm 2, Value

r/w

-19999 to -1

302

Alarm Low Set Point, Alarm 1, Value

r/w

to Alarm 1 High Set Point

321

Alarm Low Set Point, Alarm 2, Value

r/w

to Alarm 2 High Set Point

708

Alarm Messages, Alarm Output 1

r/w

0

Yes on Main Page

1

No

725

Alarm Messages, Alarm Output 2

r/w

0

Yes on Main Page

1

No

1308

Alarm Set Point, Lockout

r/w

0

Full Access

1

Read Only

2

Password

3

Hidden

706

Alarm Sides, Alarm Output 1

r/w

0

Both

1

Low

2

High

723

Alarm Sides, Alarm Output 2

r/w

0

Both

1

Low

2

High

705

Alarm Silencing, Alarm Output 1

r/w

0

No

1

Yes

722

Alarm Silencing, Alarm Output 2

r/w

0

No

1

Yes

716

Alarm Source, Alarm Output 1

r/w

0

Input 1

1

Input 2

2

Input 3

733

Alarm Source, Alarm Output 2

r/w

0

Input 1

1

Input 2

2

Input 3

702

Alarm Type, Alarm Output 1

r/w

0

Off

1

Process

2

Deviation

719

Alarm Type, Alarm Output 2

r/w

0

Off

1

Process

2

Deviation

1902

Altitude, Analog Input 2

r/w

0

0 to 2499 ft

1

2500 to 4999 ft

2

5000 ft and above

606

Analog Input 1 Decimal Point

r/w

0

0

1

00

2

000

3

0000

616

Analog Input 2 Decimal Point

r/w

0

0

1

00

2

000

3

0000

626

Analog Input 3 Decimal Point

r/w

0

0

1

00

2

000

3

0000

836

Analog Range, Retransmit Output 1

r/w

0

4 to 20mA

1

0 to 20mA

2

0 to 5V

3

1 to 5V

4

1 to 10V

837

Analog Range, Retransmit Output 2

r/w

0

4 to 20mA

1

0 to 20mA

2

0 to 5V

3

1 to 5V

4

1 to 10V

305

Autotune Channel 1

r/w

0

Tune Off

1

PID Set 1

2

PID Set 2

3

PID Set 3

4

PID Set 4

5

PID Set 5

324

Autotune Channel 2

r/w

0

Tune Off

1

PID Set 6

2

PID Set 7

3

PID Set 8

4

PID Set 9

5

PID Set 10

343

Autotune Cascade

r/w

0

Tune Off

1

PID Set 1

2

PID Set 2

3

PID Set 3

4

PID Set 4

5

PID Set 5

7 . 2

C o m m u n i c a t i o n s

Wa t l o w S e r i e s F 4 S / D

Series F4 Modbus Registers

Parameters Sorted Alphabetically

Register numbers listed are relative values. To convert to absolute values, add 40001. Registers for

profiling parameters are in a separate section at the end of this list, followed by a list of all Mod-

bus registers in numerical order. For more information about parameters, see the Index.