Operations page parameter table, Alarm set points – Watlow Series F4S/D User Manual

Page 30

background image

Active if Alarm 2 Type (Setup

Page) is set to Deviation.

322

r/w

999 (999)

0 to 30000

(0 to 30000)

Alarm 2 High Deviation

Set the deviation

above set point 2

that will trigger an

alarm.

Active if Alarm 2 Type (Setup

Page) is set to Deviation.

Active if decimal is set to 0.0

321

r/w

-999 (-999)

-99.9 (-999)

-19999 to -1

(-1 to -19999)

-.1 to -1999.9

(-1 to -19999)

Alarm 2 Low Deviation

Set the deviation

below set point 2

that will trigger an

alarm.

Active if Alarm 2 Type (Setup

Page) is set to Process.

322

r/w

to Alarm

2 Low Set Point

Alarm 2 High SP

Set high value at

which alarm is trig-

gered.

Active if Alarm 2 Type (Setup

Page) is set to Process.

321

r/w

to Alarm

2 High Set Point

Alarm 2 Low SP

Set low value at

which alarm is trig-

gered.

Active if Alarm 1 Type (Setup

Page) is set to Deviation.

Active if decimal is set to 0.0

303

r/w

999 (999)

99.9 (999)

1 to 30000

(1 to 30000)

.1 to 3000.0

(1 to 30000)

Alarm 1 High Deviation

Set the deviation

above set point 1

that will trigger an

alarm.

Active if Alarm 1 Type (Setup

Page) is set to Deviation.

Active if decimal is set to 0.0.

302

r/w

-999 (-999)

-99.9 (999)

-19999 to -1

(-1 to 19999)

-.1 to -1999.9

(-1 to 19999)

Alarm 1 Low Deviation

Set the deviation

below set point 1

that will trigger an

alarm.

Active if Alarm 1 Type (Setup

Page) is set to Process.

303

r/w

to Alarm

1 Low Set Point

Alarm 1 High SP

Set high value at

which alarm is trig-

gered.

Active if Alarm 1 Type (Setup

Page) is set to Process.

302

r/w

to Alarm

1 High Set Point

Alarm 1 Low SP

Set low value at

which alarm is trig-

gered.

Main > Operations > Alarm Set Points

Alarm Set Points

Active if Proportional Band is set

to 0 and one channel is set to

heat and the other to cool

(Setup Page).

1A

1B Set

2607 2657 [1]

2617 2667 [2]

2627 2677 [3]

2637 2687 [4]

2647 2697 [5]

r/w

3 (3)

1 to 30000

(1 to 30000)

Hysteresis x (A or B)

Define the process

variable change from

the set point re-

quired to re-energize

the output (in on-off

mode).

3 . 1 4

O p e r a t i o n s

Wa t l o w S e r i e s F 4 S / D

Operations Page Parameter Table