Operations page parameter table, Alarm set points – Watlow Series F4S/D User Manual
Page 30
![background image](/manuals/359283/30/background.png)
Active if Alarm 2 Type (Setup
Page) is set to Deviation.
322
r/w
999 (999)
0 to 30000
(0 to 30000)
Alarm 2 High Deviation
Set the deviation
above set point 2
that will trigger an
alarm.
Active if Alarm 2 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0
321
r/w
-999 (-999)
-99.9 (-999)
-19999 to -1
(-1 to -19999)
-.1 to -1999.9
(-1 to -19999)
Alarm 2 Low Deviation
Set the deviation
below set point 2
that will trigger an
alarm.
Active if Alarm 2 Type (Setup
Page) is set to Process.
322
r/w
2 Low Set Point
Alarm 2 High SP
Set high value at
which alarm is trig-
gered.
Active if Alarm 2 Type (Setup
Page) is set to Process.
321
r/w
2 High Set Point
Alarm 2 Low SP
Set low value at
which alarm is trig-
gered.
Active if Alarm 1 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0
303
r/w
999 (999)
99.9 (999)
1 to 30000
(1 to 30000)
.1 to 3000.0
(1 to 30000)
Alarm 1 High Deviation
Set the deviation
above set point 1
that will trigger an
alarm.
Active if Alarm 1 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0.
302
r/w
-999 (-999)
-99.9 (999)
-19999 to -1
(-1 to 19999)
-.1 to -1999.9
(-1 to 19999)
Alarm 1 Low Deviation
Set the deviation
below set point 1
that will trigger an
alarm.
Active if Alarm 1 Type (Setup
Page) is set to Process.
303
r/w
1 Low Set Point
Alarm 1 High SP
Set high value at
which alarm is trig-
gered.
Active if Alarm 1 Type (Setup
Page) is set to Process.
302
r/w
1 High Set Point
Alarm 1 Low SP
Set low value at
which alarm is trig-
gered.
Main > Operations > Alarm Set Points
Alarm Set Points
Active if Proportional Band is set
to 0 and one channel is set to
heat and the other to cool
(Setup Page).
1A
1B Set
2607 2657 [1]
2617 2667 [2]
2627 2677 [3]
2637 2687 [4]
2647 2697 [5]
r/w
3 (3)
1 to 30000
(1 to 30000)
Hysteresis x (A or B)
Define the process
variable change from
the set point re-
quired to re-energize
the output (in on-off
mode).
3 . 1 4
■
O p e r a t i o n s
Wa t l o w S e r i e s F 4 S / D
Operations Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear