Profiles Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
✔ NOTE: Two sets of Modbus registers contain profile informa-
tion: In edit mode, the number of the profile being edited is at
4000, and the number of the step being edited is at 4001. When
the profile is running, the number of the profile being run is at
4100, and the number of the step being run is at 4101. All run
addresses are read only.
Wa t l o w S e r i e s F 4 S / D
P r o f i l e P r o g r a m m i n g
■
4 . 1 3
✔ NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Active: Always.
4012 r/w
Event Input x (1 to 4)
Analog Input x (1 to 3)
Step Wait For…
Wait for the chosen
condition.
—
4012 r/w
—
Does not wait (0)
Wait for (1)
Step Does/Does Not Wait
Do not wait for any
condition.
… > Profile (1 to 40) > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > Wait for:
Wait for:
Active: Always.
Ch
4048 r/w [1]
4049 r/w [2]
No (0)
No (0)
Yes (1)
Guarantee Soak
Select this feature.
Active: Always.
Ch
4046 r/w [1]
4124
r
[1]
4047 r/w [2]
4125
r
[2]
[1] (0)
[2] (0)
Channel 1 PID 1 to 5
Channel 2 PID 6 to 10
[1] (0 to 4)
[2] (0 to 4)
PID Set
Select the PID set
for each channel.
Active if Step is set to Time and
controller is Dual Channel.
4045 r/w
4123 r
75 (75)
Set point low limit to
set point high limit
Set Point Channel 2
Set the target for the
Channel 2 process
value (temperature,
etc.) at the end of
this step.
Active if Step is set to Time or
Rate.
4044 r/w
4122 r
75 (75)
Set point low limit to
set point high limit
Set Point Channel 1
Set the target for the
Channel 1 process
value (temperature,
etc.) at the end of
this step.
Active if Step is set to Rate and
controller is not Dual Channel.
4043 r/w
.1
.1 to 3,000.0 degrees
per minute
(1 to 30000)
Rate
Select the rate of
change by entering
degrees per minute.
Active if Step is set to Ramp
Time or Soak.
Ch
4009 r/w [h]
4119
r
[h]
4010 r/w [m]
4120
r
[m]
4011 r/w [s]
4121
r
[s]
00:00:01
(0)
(0)
(1)
00:00:01 to 99:59:59
[h] (0 to 99)
[m] (0 to 59)
[s] (0 to 59)
Time
Set the time in
hours, minutes and
seconds.