Profiles Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

NOTE: Two sets of Modbus registers contain profile informa-
tion: In edit mode, the number of the profile being edited is at
4000, and the number of the step being edited is at 4001. When
the profile is running, the number of the profile being run is at
4100, and the number of the step being run is at 4101. All run
addresses are read only.

Wa t l o w S e r i e s F 4 S / D

P r o f i l e P r o g r a m m i n g

4 . 1 3

NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.

Active: Always.

4012 r/w

Event Input x (1 to 4)
Analog Input x (1 to 3)

Step Wait For…

Wait for the chosen

condition.

4012 r/w

Does not wait (0)
Wait for (1)

Step Does/Does Not Wait

Do not wait for any

condition.

… > Profile (1 to 40) > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > Wait for:

Wait for:

Active: Always.

Ch

4048 r/w [1]

4049 r/w [2]

No (0)

No (0)
Yes (1)

Guarantee Soak

Select this feature.

Active: Always.

Ch

4046 r/w [1]

4124

r

[1]

4047 r/w [2]

4125

r

[2]

[1] (0)
[2] (0)

Channel 1 PID 1 to 5
Channel 2 PID 6 to 10
[1] (0 to 4)
[2] (0 to 4)

PID Set

Select the PID set

for each channel.

Active if Step is set to Time and

controller is Dual Channel.

4045 r/w
4123 r

75 (75)

Set point low limit to

set point high limit

Set Point Channel 2

Set the target for the

Channel 2 process

value (temperature,

etc.) at the end of

this step.

Active if Step is set to Time or

Rate.

4044 r/w
4122 r

75 (75)

Set point low limit to

set point high limit

Set Point Channel 1

Set the target for the

Channel 1 process

value (temperature,

etc.) at the end of

this step.

Active if Step is set to Rate and

controller is not Dual Channel.

4043 r/w

.1

.1 to 3,000.0 degrees

per minute

(1 to 30000)

Rate

Select the rate of

change by entering

degrees per minute.

Active if Step is set to Ramp

Time or Soak.

Ch

4009 r/w [h]

4119

r

[h]

4010 r/w [m]

4120

r

[m]

4011 r/w [s]

4121

r

[s]

00:00:01
(0)
(0)
(1)

00:00:01 to 99:59:59
[h] (0 to 99)
[m] (0 to 59)
[s] (0 to 59)

Time

Set the time in

hours, minutes and

seconds.