Operations Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

NOTE: Press the Information Key ˆ for more task-related tips.

Active if PID Units (Setup Page)

is set to U.S. and Proportional

Band is not set to 0.

2A

2B Set

2504 2554 [6]

2514 2564 [7]

2524 2574 [8]

2534 2584 [9]

2544 2594 [10]

r/w

0.00 minutes

(0)

0.00 to 9.99 minutes

(0 to 999)

Rate x (A or B)

Set the rate time.

Active if PID Units (Setup Page)

is set to SI and Proportional

Band is not set to 0.

2A

2B Set

2503 2553 [6]

2513 2563 [7]

2523 2573 [8]

2533 2583 [9]

2543 2593 [10]

r/w

0.00 minutes

(0)

0.00 to 9.99 minutes

(0 to 999)

Derivative x (A or B)

Set the derivative

time.

Active if PID Units (Setup Page)

is set to U.S. and Proportional

Band is not set to 0.

2A

2B Set

2502 2552 [6]

2512 2562 [7]

2522 2572 [8]

2532 2582 [9]

2542 2592 [10]

r/w

0 per minute

(0)

0.00 per minute to

99.99 per minute

(0 to 9999)

Reset x (A or B)

Set the reset time in

repeats per minute.

Active if PID Units (Setup Page)

is set to SI and Proportional

Band is not set to 0.

2A

2B Set

2501 2551 [6]

2511 2561 [7]

2521 2571 [8]

2531 2581 [9]

2541 2591 [10]

r/w

0 minutes

(0)

0.00 to 99.99 minutes

(0 to 9999)

Integral x (A or B)

Set the integral time

in minutes.

Active: Always (Channel 1).

2A

2B Set

2500 2550 [6]

2510 2560 [7]

2520 2570 [8]

2530 2580 [9]

2540 2590 [10]

r/w

25°F (25)

14°C (14)

0 to 30000

(1 to 30000)

Proportional Band x (A or B)

Set the proportional

band.

Main > Operations > Edit PID > PID Set Channel 2 > PID Set x (6 to 10)

PID Set x (6 to 10)

Active if Proportional Band is set

to 0 and one channel is set to

heat and the other to cool

(Setup Page).

1A

1B Set

507 557 [1]

517 567 [2]

527 577 [3]

537 587 [4]

547 597 [5]

r/w

3 (3)

1 to 30000

(1 to 30000)

Hysteresis x (A or B)

Define the process

variable change from

the set point re-

quired to re-energize

the output (in on-off

mode).

Active if Proportional Band is not

set to 0 and one output is set to

heat and the other to cool

(Setup Page).

1A

1B Set

505 555 [1]

515 565 [2]

525 575 [3]

535 585 [4]

545 595 [5]

r/w

0

(0)

0 to 30000

(0 to 30000)

Dead Band x (A or B)

Define the effective

shift in the heating

and cooling set

points to prevent

conflict.

Active if PID Units (Setup Page)

is set to U.S. and Proportional

Band is not set to 0.

1A

1B Set

504 554 [1]

514 564 [2]

524 574 [3]

534 584 [4]

544 594 [5]

r/w

0.00 minutes

(0)

0.00 to 9.99 minutes

(0 to 999)

Rate x (A or B)

Set the rate time.