F4 modbus applications: creating a profile – Watlow Series F4S/D User Manual

Page 94

background image

7 . 1 8

C o m m u n i c a t i o n s

Wa t l o w S e r i e s F 4 S / D

*Profiles without custom-written names are referred to by

their numbers (Profile 1, Profile 2, etc.),

Create Profile

Write Modbus Register

4002=1

Set File Number

Write Modbus Register

4000=1 to 40

-Optional-

Rename Profile*

Registers 3500 thru 3899

Insert Step

Write Modbus Register

4002=2

Set Current Step Number

Write Modbus Register

4001=1 to 256

Set Step Number to where

the "End" step is located
Write Modbus Register

4001=1 to 255

Step Type

"Autostart"?

Done with

profile?

Step Type

"Time"?

Step Type

"Rate"?

Step Type

"Soak"?

Step Type

"Jump"?

No

No

No

No

Yes

Yes

Yes

Yes

Yes

See "Autostart"

Step Type sheet

for options

See "Time"

Step Type sheet

for options

See "Rate"

Step Type sheet

for options

See "Soak"

Step Type sheet

for options

See "Jump"

Step Type sheet

for options

Assumes file does not exist

Use 1 to 40

File will be placed at lowest

empty file location.

See "End"

Step Type sheet

for options

No

Yes

Done

F4 Modbus Applications: Creating a Profile