9 . 4

C a l i b r a t i o n

Wa t l o w S e r i e s F 4 S / D

Press . once at the Calibrate Input 3 prompt.

At the 4.000mA prompt press . once and to

store the 4.000mA input press > once.

10. Enter 20.000mA from the current source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 3 prompt

(Factory Page). At the 20.000mA prompt press
.

once and to store the 20.000mA input press

>

once.

11. Rewire for operation and verify calibration.

Process Output Procedure

Equipment
• Precision volt/ammeter with 3.5-digit resolu-

tion.

Output 1A Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Milliamperes
2. Connect the volt/ammeter to terminals 42 (+)

and 43 (-).

3. Press the Right Key . at the Calibrate Out-

put 1A prompt. At the 4.000mA prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 4.000mA. Press . to store the value.

4. Press the Right Key . at the Calibrate Out-

put 1A prompt. At the 20.000mA prompt press
.

once. Use the Up Key > or the Down Key

<

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 20.000mA. Press . to store the val-

ue.

Volts
5. Connect the volt/ammeter to terminals 44 (+)

and 43 (-).

6. Press the Right Key . at the Calibrate Out-

put 1A prompt. At the 1.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 1.000V. Press . to store the value.

7. Press the Right Key . at the Calibrate Out-

put 1A prompt. At the 10.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 10.000V. Press . to store the value.

8. Rewire for operation and verify calibration.

Output 1B Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Milliamperes
2. Connect the volt/ammeter to terminals 39 (+)

and 40 (-).

3. Press the Right Key . at the Calibrate Out-

put 1B prompt. At the 4.000mA prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 4.000mA. Press . to store the value.

4. Press the Right Key . at the Calibrate Out-

put 1B prompt. At the 20.000mA prompt press
.

once. Use the Up Key > or the Down Key

<

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 20.000mA. Press . to store the val-

ue.

Volts
5. Connect the volt/ammeter to terminals 41 (+)

and 40 (-).

6. Press the Right Key . at the Calibrate Out-

put 1B prompt. At the 1.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 1.000V. Press . to store the value.

7. Press the Right Key . at the Calibrate Out-

put 1B prompt. At the 10.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 10.000V. Press . to store the value.

8. Rewire for operation and verify calibration.