Factory page parameter table, Restore input x (1 to 3) calibration, Calibrate input x (1 to 3) – Watlow Series F4S/D User Manual
Page 114
Factory Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
✔ NOTE:
Press the Information Key
ˆ for more task-related tips.
9 . 8
■
C a l i b r a t i o n
Wa t l o w S e r i e s F 4 S / D
1601 w
Modbus:
Input 1 (0)
Input 2 (1)
Input 3 (2)
Restore Input x (1 to 3)
Calibration
Restores original
factory calibration
values.
Main > Factory > Calibration / Restore Input x (1 to 3) Calibration
Restore Input x (1 to 3) Calibration
Active: Always.
Output
1607
[1A]
1612
[1B]
1617
[2A]
1622
[2B]
Rexmit
1627
[1]
1632
[2]
w
10.000V
(10000)
0.000 to 12.000V
(0 to 12000)
10.000V
Store 10.000V cali-
bration for the pro-
cess output.
Active: Always.
Output
1606
[1A]
1611
[1B]
1616
[2A]
1621
[2B]
Rexmit
1626
[1]
1631
[2]
w
1.000V
(1000)
0.000 to 3.000V
(0 to 3000)
1.000V
Store 1.000V cali-
bration for the pro-
cess output.
Active: Always.
Output
1605
[1A]
1610
[1B]
1615
[2A]
1620
[2B]
Rexmit
1625
[1]
1630
[2]
w
20.000mA
(20000)
0.000 to 24.000mA
(0 to 24000)
20.000mA
Store 20mA calibra-
tion for the process
output.
Active: Always.
Output
1604
[1A]
1609
[1B]
1614
[2A]
1619
[2B]
Rexmit
1624
[1]
1629
[2]
w
4.000mA
(4000)
0.000mA to 6.000mA
(0 to 6000)
4.000mA
Store 4mA calibra-
tion for the process
output.
Main > Factory > Calibration / Calibrate Output x (1A, 1B, 2A, 2B) and Retransmit x (1 and 2)
Calibrate Output x (1A, 1B, 2A, 2B ) and Retransmit x (1 and 2)
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (11)
20.000mA
Store 20mA calibra-
tion for the process
input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (10)
4.000mA
Store 4mA calibra-
tion for the process
input.
Main Page > Factory > Calibration > Calibrate Input x (1 to 3)
Calibrate Input x (1 to 3)