Factory Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

*The tenth character of your model number determines

what prompts appear and what input resistance values to

use for the RTD calibration.

F4_ _-_ _ _ _-_(1 to 4)

RG

: 15.00 and 380.00

F4_ _-_ _ _ _-_(5 to 8)

RG

: 240.00 and 6080.00

NOTE:
For more information about how parameter settings affect

the controller’s operation, see Features Chapter.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (9)

10.000V

Store 10.000V cali-

bration for the pro-

cess input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (8)

0.000V

Store 0.000V calibra-

tion for the process

input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (7)

6080.0 Ohms*

Store 6080.00

cali-

bration for the 500

or 1k

RTD input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (7)

380.0 Ohms*

Store 380.00

cali-

bration for the 100

RTD input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (6)

240.0 Ohms*

Store 240.00

cali-

bration for the 500

or 1k

RTD input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (6)

15.0 Ohms*

Store 15.00

calibra-

tion for the 100

RTD input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (5)

Lead

Store calibration for

lead resistance.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (4)

Ground

Store calibration for

ground at gains of 1

and 32.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (3)

32°F Type J

Store 32°F type J

calibration.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (2)

50.00mV Thermocouple

Store 50.000mV cali-

bration for the ther-

mocouple input.

Active: Always.

Input

1603

[1]

1608

[2]

1613

[3]

w

Yes (1)

0.00mV Thermocouple

Store 0.000mV cali-

bration for the ther-

mocouple input.

Main Page > Factory > Calibration > Calibrate Input x (1 to 3)

Calibrate Input x (1 to 3)