C a l i b r a t i o n
■
9 . 7
Factory Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
*The tenth character of your model number determines
what prompts appear and what input resistance values to
use for the RTD calibration.
F4_ _-_ _ _ _-_(1 to 4)
RG
: 15.00 and 380.00
Ω
F4_ _-_ _ _ _-_(5 to 8)
RG
: 240.00 and 6080.00
Ω
✔ NOTE:
For more information about how parameter settings affect
the controller’s operation, see Features Chapter.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (9)
10.000V
Store 10.000V cali-
bration for the pro-
cess input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (8)
0.000V
Store 0.000V calibra-
tion for the process
input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (7)
6080.0 Ohms*
Store 6080.00
Ω
cali-
bration for the 500
Ω
or 1k
Ω
RTD input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (7)
380.0 Ohms*
Store 380.00
Ω
cali-
bration for the 100
Ω
RTD input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (6)
240.0 Ohms*
Store 240.00
Ω
cali-
bration for the 500
Ω
or 1k
Ω
RTD input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (6)
15.0 Ohms*
Store 15.00
Ω
calibra-
tion for the 100
Ω
RTD input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (5)
Lead
Store calibration for
lead resistance.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (4)
Ground
Store calibration for
ground at gains of 1
and 32.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (3)
32°F Type J
Store 32°F type J
calibration.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (2)
50.00mV Thermocouple
Store 50.000mV cali-
bration for the ther-
mocouple input.
Active: Always.
Input
1603
[1]
1608
[2]
1613
[3]
w
Yes (1)
0.00mV Thermocouple
Store 0.000mV cali-
bration for the ther-
mocouple input.
Main Page > Factory > Calibration > Calibrate Input x (1 to 3)
Calibrate Input x (1 to 3)