Setup page parameter table – Watlow Series F4S/D User Manual

Page 57

background image

Wa t l o w S e r i e s F 4 S / D

S e t u p

5 . 9

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set, Ch)

Parameters to Appear

NOTE:
For more information about how parameter settings affect the con-

troller’s operation, see the Features Chapter.

Active: Always, except when Cas-

cade is set to Process Cascade

or Deviation Cascade this is

masked for Analog Input 1.

Input

602

[1]

612

[2]

622

[3]

r/w

Depends on sensor.

Set Point Low Limit

Set limit for mini-

mum set point.

Active if Ch2 Output Disable is

set to Yes.

698 r/w

Sensor range high to

In1 Temp Low + 1

Enter In1 Temp High

Choose the highest

temperature at

which the channel 2

output is active.

Active if Ch2 Output Disable is

set to Yes.

697 r/w

Sensor range low to

In1 Temp High - 1

Enter In1 Temp Low

Choose the lowest

temperature at

which the channel 2

output is active.

Active if Analog Input 2, Sensor

is set to Process and Units is

set to %rh and Analog Input 1,

Units is set to Temperature.

696 r/w

No (0)

No (0)

Yes (1)

Ch2 Output Disable?

Disables Channel 2

outside the range

defined by Enter In1

Temp Low and

Enter In1 Temp

High.

Active if Sensor Type is set to

Process.

Input

693

[1]

694

[2]

695

[3]

r/w

Normal (0)

Normal Scaling (0)

Scale Inversion (1)

(Scale High corre-

sponds to the lowest

process value, and

Scale Low corre-

sponds to the highest

process value.)

Choose Scaling

Select normal or in-

verse scaling.

Active if Sensor Type is set to

Process.

Input

681

[1]

683

[2]

685

[3]

r/w

Depends on sensor and

decimal point selec-

tion.

Scale High

Set unit value for

high end of current

or voltage range.

Active if Sensor Type is set to

Process.

Input

680

[1]

682

[2]

684

[3]

r/w

Depends on sensor and

decimal point selec-

tion.

Scale Low

Set unit value for

low end of current or

voltage range.

Active if Sensor Type is set to

Process.

Input

606

[1]

616

[2]

626

[3]

r/w

0 (0)

0 (0)

0.0 (1)

0.00 process (2)

0.000 process (3)

Decimal

Set the decimal

point for input.

Active if Sensor Type is set to

Process.

Input

608

[1]

618

[2]

628

[3]

r/w

Temperature

(0)

Temperature (0)

%rh (1)

psi (2)

units (3)

Units

Select the units of

measure for the

input.

Active if Analog Input 2 Type is

Wet Bulb-Dry Bulb.

1902 r/w

0 to 2499 ft

(0)

0 to 2499 ft (0)

2500 to 4999 ft (1)

5000 ft and above (2)

Altitude

Select an elevation

to compensate for

wet bulb evapora-

tion rates.