Output 2A Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Milliamperes
2. Connect the volt/ammeter to terminals 36 (+)

and 37 (-).

3. Press the Right Key . at the Calibrate Out-

put 2A prompt. At the 4.000mA prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 4.000mA. Press . to store the value.

4. Press the Right Key . at the Calibrate Out-

put 2A prompt. At the 20.000mA prompt press
.

once. Use the Up Key > or the Down Key

<

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 20.000mA. Press . to store the val-

ue.

Volts
5. Connect the volt/ammeter to terminals 38 (+)

and 37 (-).

6. Press the Right Key . at the Calibrate Out-

put 2A prompt. At the 1.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 1.000V. Press . to store the value.

7. Press the Right Key . at the Calibrate Out-

put 2A prompt. At the 10.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 10.000V. Press . to store the value.

8. Rewire for operation and verify calibration.

Output 2B Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Milliamperes
2. Connect the volt/ammeter to terminals 33 (+)

and 34 (-).

3. Press the Right Key . at the Calibrate Out-

put 2B prompt. At the 4.000mA prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 4.000mA. Press . to store the value.

4. Press the Right Key . at the Calibrate Out-

put 2B prompt. At the 20.000mA prompt press
.

once. Use the Up Key > or the Down Key

<

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 20.000mA. Press . to store the val-

ue.

Volts
5. Connect the volt/ammeter to terminals 35 (+)

and 34 (-).

6. Press the Right Key . at the Calibrate Out-

put 2B prompt. At the 1.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 1.000V. Press . to store the value.

7. Press the Right Key . at the Calibrate Out-

put 2B prompt. At the 10.000V prompt press .

once. Use the Up Key > or the Down Key <

to adjust the display to the reading on the

volt/ammeter. The controller should stabilize

within one second. Repeat until the volt/amme-

ter reads 10.000V. Press . to store the value.

8. Rewire for operation and verify calibration.

Retransmit Output Procedure

Equipment
• Precision volt/ammeter with 3.5-digit resolu-

tion.

Retransmit 1 Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Milliamperes
2. Connect the volt/ammeter to terminals 50 (+)

and 49 (-).

3. Press the Right Key . at the Calibrate

Rexmit 1 prompt. At the 4.000mA prompt press
.

once. Use the Up Key > or the Down Key