Alarm Set Points

The Series F4 includes two alarm outputs, which

can be programmed as process or deviation alarms.
Process alarms notify the operator when process

values exceed or fall below Alarm Low and Alarm

High Set Points. Deviation alarms notify the opera-

tor when the process has deviated from the set

point beyond the deviation limits. For more infor-

mation, see the Features Chapter. To set up the

alarms, see the Setup Chapter.
Alarm set points are the points at which alarms

switch on or off, depending on the alarm setting.

Alarm set points can be viewed or changed in the

Alarm Set Point Menus (Operations Page).
The Alarm High Set Point

defines the high tem-

perature that, if exceeded, will trigger an alarm.

This temperature must be higher than the alarm

low set point and lower than the high limit of the

sensor range.
The Alarm Low Set Point

defines the low tem-

perature that, if exceeded, will trigger an alarm.

This temperature must be lower than the alarm

high set point and higher than the low limit of the

sensor range.

TIP:
You may want to set up the alarms with names that will
identify the alarm conditions. See the Setup Page.

To Clear an Alarm or Error

In an alarm condition, an alarm message will ap-

pear on the Main Page (if this option has been se-

lected on the Setup Page). To silence it, move the

cursor to the alarm message and press the Right

Key . . A pop-up message will confirm the silenc-

ing of the alarm, and the indicator light will go off.
When the condition causing the error or alarm is

corrected, return to the error or alarm message on

the Main Page, and press the Right Key again. A

pop-up message confirms the alarm is unlatched.

Auto-tune PID

In autotuning, the controller automatically selects

the PID parameters for optimal control, based on

the thermal response of the system. In the Series

F4, five sets of PID values are available for each

channel of the controller: sets 1 to 5 for channel 1,

and sets 6 to 10 for channel 2. Default PID values

exist for all PID sets, although these values typi-

cally do not provide optimal control. PID values

can be auto-tuned or adjusted manually. When au-

totuning is complete, the PID values will be stored

in the Edit PID Menu.

NOTE:
PID Set 1 for Channel 1 and PID Set 6 for Channel 2
are used in the Static Set Point mode.

Autotuning Procedure

Autotuning cannot be initiated while a profile is

running. It can only be initiated in the static set

point control mode.

1. Before initiating auto-tune, go to the System

Menu (Setup Page), and set the Channel 1 or 2

Autotune Set Point to the percentage of set point

you choose to begin with. This percentage is

based on your knowledge of the system and how

much overshoot or undershoot there is likely to

be in on-off control.

In the Custom Main Page, select to display Tune

Status 1 and Tune Status 2. This displays Tune

Status in the Main Page.

2. Go to the Main Page and set the static set point.

3. Go to the Autotune PID Menu (Operations Page)

and choose the channel to auto-tune and the PID

set in which to store the settings. A message will

be displayed on the Main Page during the auto-

tuning process. (Auto-tune cannot be initiated

when a profile is running. It can only be initiated

in the static set point mode.)

4. When autotuning is complete, the controller will

store the values for optimum control in the PID

set specified.

NOTE:
While the controller is autotuning, profiles cannot be run
and only the Profiles Page and Operation Page of the
software can be entered.

ç

CAUTION: Choose an auto-tune set point value that will
protect your product from possible damage from overshoot
or undershoot during the autotuning oscillations. If the
product is sensitive, select the auto-tune set point very
carefully to prevent product damage.

For additional information about autotuning and proportion-
al, integral and derivative control, see the Features Chapter.

Edit PID

Edit PID is useful when Auto-tune PID does not

provide adequate control. Each of the PID parame-

ters can be adjusted manually:
Proportional Band:

Define a band for PID con-

trol, entered in degrees or units. Lower values in-

crease gain, which reduces droop but can cause os-

cillation. Increase the proportional band to elimi-

nate oscillation.