1306

Autotune PID, Lockout

r/w

0

Full Access

1

Read Only

2

Password

3

Hidden

304

Autotune Set Point, Channel 1, Value

r/w

50 to 150

(expressed in %)

323

Autotune Set Point, Channel 2, Value

r/w

50 to 150

(expressed in %)

2062

Boost Cool % Power, Digital Output 7

r/w

-100 to 0 for Cool

(expressed in %)

2064

Boost Cool Delay On Time, Digital Output 7

r/w

0 to 9999 seconds

2062

Boost Cool Power

r/w

Value

2064

Boost Cool Time

r/w

Value

2052

Boost Heat % Power, Digital Output 6

r/w

0 to 0 for Heat

(expressed in %)

2054

Boost Heat Delay On Time, Digital Output 6

r/w

0 to 9999 seconds

2052

Boost Heat Power

r/w

Value in %

2054

Boost Heat Time

r/w

Value in seconds

605

Calibration Offset, Analog Input 1

r/w

-19999 to 30000

615

Calibration Offset, Analog Input 2

r/w

-19999 to 30000

625

Calibration Offset, Analog Input 3

r/w

-19999 to 30000

1922

Cascade Inner Set Point

r
1925

Cascade Type

r/w

0

No Cascade

1

Process Cascade

2

Deviation Cascade

1926

Cascade, Range Low

r/w

Depends on Sensor

1927

Cascade, Range High

r/w

Depends on Sensor

1330-33 Change Password
r/w

ASCII codes 0-9, A-Z

1501

CJC1 AtoD, Diagnostics

r

HHHH

see In 1 AD

1500

CJC1 Temp, Diagnostics

r

value

1532

CJC2 AtoD, Diagnostics

r

HHHH

1531

CJC2 Temp, Diagnostics

r

value

312

Clear Alarm 1, Key Press Simulation

w

write any value

331

Clear Alarm 2, Key Press Simulation

w

write any value

311

Clear Error 1, Key Press Simulation

w

write any value

330

Clear Error 2, Key Press Simulation

w

write any value

349

Clear Error 3, Key Press Simulation

w

write any value

1315

Clear Locks

0

yes

2046

Complementary Output, Digital Output 5

0

1A

1

1B

2

2A

3

2B

2073

Compressor Off % Power, Digital Output 8

r/w

Compressor On % Power to 100%

2075

Compressor Off Delay, Digital Output 8

r/w

0 to 9999 seconds

2072

Compressor On % Power, Digital Output 8

r/w

-100 to 100

(expressed in percent)

2074

Compressor On Delay, Digital Output 8

r/w

1 to 9999 seconds

Control Output Calibration — see Process Output Calibration

700

Control Output 1A Function

r/w

1

Heat

2

Cool

717

Control Output 1B Function

r/w

0

Off

1

Heat

2

Cool

734

Control Output 2A Function

r/w

1

Heat

2

Cool

751

Control Output 2B Function

r/w

0

Off

1

Heat

2

Cool

1920

Current Date, Day

r/w

1 to 31

1919

Current Date, Month

r/w

1 to 12

1921

Current Date, Year

r/w

1998 to 2035

1916

Current Time, Hour

r/w

0 o 23

1917

Current Time, Minutes

r/w

0 to 59

1918

Current Time, Seconds

r/w

0 to 59

1400-15 Custom Main Page Parameters (P1 to P16)
r/w

0

None

1

Input I Value

2

Input 2 Value

3

Input 2 Value

4

Set Point 1

5

Set Point 2

6

% Power 1

7

% Power 2

8

Tune Status 1

9

Tune Status 2

10 Time
11 Date
12 Digital Inputs
13 Digital Outputs
14 Time Remaining
15 Current File
16 Current Step
17 Active Ch1 PID Set
18 Active Ch2 PID Set
19 Last Jump Step
20 Jump Count
21 Wait For Status
22 Step Type
23 Target Set Point 1
24 Target Set Point 2
25 Internal Cascade Set Point
26 Custom Message 1
27 Custom Message 2
28 Custom Message 3
29 Custom Message 4
30 Input1 Cal. Offset
31 Input2 Cal. Offset
32 Input3 Cal. Offset

4501-18 Custom Message 1
r/w
4521-38 Custom Message 2
r/w
4541-58 Custom Message 3
r/w
4561-78 Custom Message 4
r/w
509

Cycle Time (type), Control Output 1A

r/w

0

Variable Burst

1

Fixed Time

506

Cycle Time Value, Control Output 1A

r/w

number

559

Cycle Time (type), Control Output 1B

r/w

0

Variable Burst

1

Fixed Time

556

Cycle Time Value, Control Output 1B

r/w

number

2509

Cycle Time (type), Control Output 2A

r/w

0

Variable Burst

1

Fixed Time

2506

Cycle Time Value, Control Output 2A,

r/w

number

2559

Cycle Time (type), Control Output 2B

0

Variable Burst

1

Fixed Time

Wa t l o w S e r i e s F 4 S / D

C o m m u n i c a t i o n s

7 . 3

NOTE:
For more information about

parameters, see the Index.