beautypg.com

Set lockout menu parameter table, Set lockout – Watlow Series F4S/D User Manual

Page 105

background image

Wa t l o w S e r i e s F 4 S / D

S e c u r i t y a n d L o c k s

8 . 3

NOTE: For more information about how parameter settings

affect the controller’s operation, see the Features Chapter.

Set Lockout Menu Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

1315 w

Yes (0)

Clear Locks

Unlock set point

and all pages and

menus.

Active: Always.

1314 r/w

Yes (0)
No (1)

Set/Change Password

Reset or change

password. Choose

Yes to change the

password.

Active: Always.

1303 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)

Factory Page

Limit access to this

page.

Active: Always.

1302 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Setup Page

Limit access to this

page.

Active: Always.

1309 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Profile Page

Limit access to this

page.

Active: Always.

1308 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Alarm Set Point

Limit access to this

menu.

Active: Always.

1307 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Edit PID

Limit access to this

menu.

Active: Always.

1306 r/w

Full Access

Full Access (0)
Read Only (1)
Password (2)
Hidden (3)

Operations, Autotune PID

Limit access to this

menu.

Active: Always.

1300 r/w

Full Access

Full Access (0)
Read Only (1)

Set Point

Set the set point

access level.

Main > Factory > Set Lock

Set Lockout