Setup page parameter table, System – Watlow Series F4S/D User Manual
Page 55
![background image](/manuals/359283/55/background.png)
Wa t l o w S e r i e s F 4 S / D
S e t u p
■
5 . 7
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set, Ch)
Parameters to Appear
✔ NOTE:
For more information about how parameter settings affect the con-
troller’s operation, see the Features Chapter.
Active: Always.
1206 r/w
Continue (0)
Continue (0)
Hold (1)
Terminate (2)
Reset (3)
Idle Set Point 1 (4)
Idle Set Point 2 (5)
Power-Out Action
Choose controller re-
sponse to power out-
age while running a
profile.
–
1213 r/w
10 seconds
(10)
0 to 30000 seconds
(0 to 30000)
Power-Out Time
Define a power out-
age in seconds.
–
Channel
904
[1]
907
[2]
r/w
Off (0)
Off (0)
On (1)
Open Loop Channel x (1 or 2)
Select whether to
turn off outputs and
display an error
message.
Active: Always (1).
Active if controller is Dual
Channel (2).
Fail
903
[1]
906
[2]
r/w
0% (0)
0 to 100% Heat only
0 to 100% Cool only
-100% to +100%
Cool/Heat or
Heat/Cool
Input x Fail (1 or 2)
Enter percent of
power supplied to
the output if analog
input sensor fails.
Active: Always (1).
Active if controller is Dual
Channel (2).
Point
304
[1]
323
[2]
r/w
90% (90)
50 to 150% (50 to 150)
Channel x Autotune Set
Point (1 or 2)
Set percent of set
point to auto-tune to.
Active: Always.
1923 r/w
Yes, Upper
Display (1)
No, Upper Display (0)
Yes, Upper Display (1)
Show °F or °C
Choose whether to
display or hide °C or
°F in top display.
Active: Always.
901 r/w
°F (0)
°F (0)
°C (1)
°F or °C
Choose temperature
scale.
Active: Always.
900 r/w
U S (Reset/
Rate) (0)
U S (Reset/Rate) (0)
SI (Integral/Derivative)
(1)
PID Units
Choose units for PID
control.
Active: Always.
Time
1919 [mm]
1920 [dd]
1921 [yy]
r/w
current date
M/D/Y
01/01/1998 to
12/31/2035
[mm] (1 to 12)
[dd] (1 to 31)
[yy] (1998 to 2035)
Current Date
Enter actual date.
Active: Always.
Time
1916 [hh]
1917 [mm]
1918 [ss]
r/w
current time
hh:mm:ss
00:00:00 to 23:59:59
[hh] (0 to 23)
[mm] (0 to 59)
[ss] (0 to 59)
Current Time
Enter actual time.
(24-hour-clock)
Active: Always (1).
Active if controller is Dual Chan-
nel (2).
Band
1205
[1]
1212
[2]
r/w
1
Decimal choice
dependent:
1 to 30000, or
.1 to 3000.0, or
.01 to 300.0, or
.001 to 30.0
(1 to 30000)
Guarantee Soak Band
x (1 or 2)
Select value above
and below set point
to define the soak
band.
Main > Setup > System
System