beautypg.com

Pi control, Pid control, Dead band – Watlow Series F4S/D User Manual

Page 69: Proportional plus integral (pi) control, Proportional integral derivative (pid) control

background image

Wa t l o w S e r i e s F 4 S / D

F e a t u r e s

6 . 5

Proportional plus Integral (PI) Control

The droop caused by proportional control (reset)

can be corrected by adding integral control. When

the system settles down the integral value is tuned

to bring the temperature or process value closer to

the set point. Integral determines the speed of the

correction, but this may increase the overshoot at

startup or when the set point is changed. Too much

integral action will make the system unstable. Inte-

gral is cleared when the process value is outside of

the proportional band.
Integral (if units are set to SI) is measured in min-

utes per repeat. A low integral value causes a fast

integrating action.
Reset rate (if units are set to U.S.) is measured in

repeats per minute. A high reset value causes a fast

integrating action.
Location in software: Operations Page > Edit PID >

PID Set Channel x (1 or 2) > PID Set x (1 to 5) or

(6 to 10).

Figure 6.5a — Proportional Plus Integral Control.

Time

Temperature

Set Point

Proportional Band

Droop corrected

Droop

Proportional Integral Derivative (PID)
Control

Use derivative rate control to minimize overshoot

in a PI-controlled system. Derivative adjusts the

output based on the rate of change in the tempera-

ture or process value. Too much derivative will

make the system sluggish.
Location in software: Operations Page > Edit PID >

PID Set Channel x (1 or 2) > PID Set x (1 to 5) or (6

to 10).

Figure 6.5b — PID Control.

Time

Temperature

Set Point

Reduced Overshoot

Proportional Band

Proportional Band x 2

Heating slows

Dead Band

In a multiple PID application the dead bands above

and below the set point can save an application's

energy and wear by maintaining process tempera-

ture within acceptable ranges. Shifting the effective

cooling set point and heating set point keeps the

two systems from fighting each other.
Proportional action ceases when the process value

is within the dead band. Integral action continues

to bring the process temperature to the set point.

When the dead band value is zero, the heating ele-

ment activates when the temperature drops below

the set point, and the cooling element switches on

when the temperature exceeds the set point.
Location in software: Operations Page > Edit PID

>PID Set Channel x (1 or 2) > PID Set x (1 to 5) or

6 to 10).

Figure 6.5c — Cooling Dead Band.

Time

Temperature

Heating Set Point

Heating Proportional Band

Cooling Dead Band

Cooling Set Point

Cooling Proportional Band