Profiles page parameter table, Jump, Pid set – Watlow Series F4S/D User Manual
Page 47
Profiles Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
Wa t l o w S e r i e s F 4 S / D
P r o f i l e P r o g r a m m i n g
■
4 . 1 5
✔ NOTE: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.
Active: Always.
4060 r/w
All Off (2)
Hold (0)
Control Off (1)
All Off (2)
Idle (3)
Action
Select what state
the controller will be
in at the end of the
profile.
Main > Profiles > Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > End
End
Active: Always.
4052 r/w
1 (1)
1 to 999
(1 to 999)
Number of Repeats*
Set number of times
to repeat the chosen
Jump.
Active: Always.
4051 r/w
1 (1)
1 to 256
(1 to 256)
Step x (1 to 256)
Select number of
steps to jump to.
—
4050 r/w
—
1 to 40 or name
(1 to 40)
Jump To Profile
Select name or num-
ber of profile to jump
to.
\Main > Profiles > Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Jump Step
Jump
Active if controller is Dual
Channel.
4047 r/w
4125 r
PID Set 6 (0)
PID Set 6 (5)
PID Set 7 (6)
PID Set 8 (7)
PID Set 9 (8)
PID Set 10 (9)
Channel 2
Select a PID set for
channel 2.
Active: Always.
4046 r/w
4124 r
PID Set 1 (0)
PID Set 1 (0)
PID Set 2 (1)
PID Set 3 (2)
PID Set 4 (3)
PID Set 5 (4)
Channel 1
Select a PID set for
channel 1.
… > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > PID Set
PID Set
*
✔ NOTE:
If a power out condition occurs during a profile and more than 20 jump steps are stored in the F4’s Profile Program
memory, the controller will terminate the profile and turn off all outputs if Continue, Hold or Terminate was selected as
the Power Out action. If Profile Reset or Go to Idle Set Point was selected, the controller will take those actions. A pop-
up message will warn of this when the 21st jump step is programmed
✔ NOTE: Two sets of Modbus registers contain profile information: In edit mode, the number of the profile being edit-
ed is at 4000, and the number of the step being edited is at 4001. When the profile is running, the number of the pro-
file being run is at 4100, and the number of the step being run is at 4101. All run addresses are read only.