Profiles Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

Wa t l o w S e r i e s F 4 S / D

P r o f i l e P r o g r a m m i n g

4 . 1 5

NOTE: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.

Active: Always.

4060 r/w

All Off (2)

Hold (0)
Control Off (1)
All Off (2)
Idle (3)

Action

Select what state

the controller will be

in at the end of the

profile.

Main > Profiles > Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > End

End

Active: Always.

4052 r/w

1 (1)

1 to 999
(1 to 999)

Number of Repeats*

Set number of times

to repeat the chosen

Jump.

Active: Always.

4051 r/w

1 (1)

1 to 256
(1 to 256)

Step x (1 to 256)

Select number of

steps to jump to.

4050 r/w

1 to 40 or name
(1 to 40)

Jump To Profile

Select name or num-

ber of profile to jump

to.

\Main > Profiles > Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Jump Step

Jump

Active if controller is Dual

Channel.

4047 r/w
4125 r

PID Set 6 (0)

PID Set 6 (5)
PID Set 7 (6)
PID Set 8 (7)
PID Set 9 (8)
PID Set 10 (9)

Channel 2

Select a PID set for

channel 2.

Active: Always.

4046 r/w
4124 r

PID Set 1 (0)

PID Set 1 (0)
PID Set 2 (1)
PID Set 3 (2)
PID Set 4 (3)
PID Set 5 (4)

Channel 1

Select a PID set for

channel 1.

… > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step > PID Set

PID Set

*

NOTE:

If a power out condition occurs during a profile and more than 20 jump steps are stored in the F4’s Profile Program

memory, the controller will terminate the profile and turn off all outputs if Continue, Hold or Terminate was selected as

the Power Out action. If Profile Reset or Go to Idle Set Point was selected, the controller will take those actions. A pop-

up message will warn of this when the 21st jump step is programmed

NOTE: Two sets of Modbus registers contain profile information: In edit mode, the number of the profile being edit-
ed is at 4000, and the number of the step being edited is at 4001. When the profile is running, the number of the pro-
file being run is at 4100, and the number of the step being run is at 4101. All run addresses are read only.