beautypg.com

Cascade, Cascade setup procedure, Cascade autotuning procedure – Watlow Series F4S/D User Manual

Page 22

background image

3 . 6

O p e r a t i o n s

Wa t l o w S e r i e s F 4 S / D

Cascade

Cascade control is available on the Series F4 con-

trollers. For background information about cascade

control, see the Features Chapter.
Select cascade control through the Analog Input 3

Menu (Setup Page) and choose Process Cascade or

Deviation Cascade. To set the range for the Process

Cascade Inner Loop set point, use Low and High

Range settings. These are independent of the Chan-

nel 1 set point. Deviation Cascade uses Deviation

Low and High settings that are referenced to the

Channel 1 set point.
Deviation Cascade is used in applications with large

set point ranges or where limiting heating or cooling

equipment temperatures is required.
When tuning a cascade system, the inner loop must

be tuned first. The inner loop comprises outputs 1A

and 1B and the Analog Input 1 sensor, which usually

measures the energy source temperature. The output

device controls a power switching device, which in

turn switches the heating and cooling. The set point

for the inner loop is generated by the outer loop. For

Process Cascade, this will have a range between the

Cascade Low Range and Cascade High Range.

Cascade Setup Procedure

1. First, configure Analog Input 3, Cascade Low

Range and Cascade High Range.
Go to the Analog Input 3 Menu (Setup Page).

Choose Process or Deviation Cascade. Deviation

Cascade references Channel 1 set point allowing a

range above and below the current control set

point. For Process Cascade control of a heat/cool or

cool only system, set the Cascade Low Range to a

value slightly lower than the lowest temperature

desired in the chamber. For heat-only systems, set

the Cascade Low Range to a value slightly lower

than the ambient temperature; otherwise the heat

output will never turn fully off.
For heat/cool or heat only systems , set the Cas-

cade High Range to a value slightly higher than

the highest temperature desired in the chamber.

For cool-only systems, set the Cascade High Range

to a value slightly higher than the ambient tem-

perature; otherwise the cooling will never fully

turn off.

2. Next, configure the controller to tune and display

data for the outer loop. To view Inner Loop Set

Point in the upper display, go to the Setup Page,

Custom Main Page Menu, select the Inner Set

point as one of the parameters, P1 to P16, to be

displayed in the Main Page.
To also view Analog Input 3 in the upper display,

go to the Setup Page, Process Display Menu, and

choose Alternating. Under Set Display Time,

choose a duration for the display of the Input 1 and

Input 3 variables.

Cascade Autotuning Procedure

1. Go to Setup Page, Custom Main Page Menu.

Choose Tune Status 1 and Tune Status 2 to ap-

pear as 2 of the 16 parameters that can be dis-

played on the Main Page. The Main Page will now

display the status of the autotuning process.

2. Autotune the inner loop. Go to the Autotune PID

Menu (Operations Page), and select Cascade In-

ner-loop. Choose Cascade Inner Loop PID Set 1 to

5, where PID values will be stored after autotun-

ing. Autotuning begins when you choose the PID

set. While autotuning, the F4 controller will con-

trol the energy source in an on-off mode to a tem-

perature equal to the Cascade High Range setting

x Channel 1 Autotune Set Point. For best results,

use proportional control only on the inner loop.

3. Next, autotune the outer loop. Go to the Auto-

tune PID Menu (Operations Page). Choose

Cascade Outer Loop, then choose Outer Loop PID

set 1 to 5, where PID values will be stored after

autotuning. Autotuning begins when you choose

the PID set. While autotuning, the outer loop will

be controlled in an on-off mode at a set point

equal to static set point x Ch 1 Autotune Set

Point. In most cases, the autotuning feature will

tune for acceptable control. If not, manually tune

the outer loop (step 4 below). Before manually

tuning, record the values generated by the auto-

tuning feature.

4. To manually tune the outer loop, go to the Edit

PID Menu (Operations Page). Choose Cascade

Outer Loop, then choose Outer Loop PID set 1 to

5. Begin manual tuning by setting the Propor-

tional Band to 5, Integral (Reset) to 0, and Rate

to 0. Establish the desired set point and let the

system stabilize. When the system stabilizes,

watch the Inner Loop Set Point on the Main

Page. If this value fluctuates, increase the pro-

portional band until it stabilizes. Adjust the pro-

portional band in 3° to 5° increments, allowing

time for the system to stabilize between adjust-

ments.

5. When Input 1 has stabilized, watch the percent

power on the Main Page. It should be stable,

±2%. At this point, the process temperature

should also be stable, but it will exhibit droop

(stabilized below set point). The droop can be

eliminated with Integral (reset).

6. Start with an integral setting of 99.9 minutes,

and allow 10 minutes for the process tempera-

ture to come up to set point. If it has not,

decrease the setting by half and wait another 10

minutes. Then halve the setting again and wait

another 10 minutes until the process value

equals the set point. If the process becomes

unstable, the integral value is too small. Increase

it until the process stabilizes.