Profiles Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
[I/O, Set, Ch]
Parameters to Appear
✔ NOTE: To edit profiles through serial communications, see p. 7.17,
✔ NOTE: Two sets of Modbus registers contain profile information:
In edit mode, the number of the profile being edited is at 4000, and
the number of the step being edited is at 4001. When the profile is
running, the number of the profile being run is at 4100, and the
number of the step being run is at 4101. All run addresses are read
only.
4 . 1 2
■
P r o f i l e P r o g r a m m i n g
Wa t l o w S e r i e s F 4 S / D
Active if digital outputs are con-
figured as events.
Dig
Out
4030 r/w [1]
4111
r
[1]
4031 r/w [2]
4112
r
[2]
4032 r/w [3])
4113
r
[3])
4033 r/w [4]
4114
r
[4]
4034 r/w [5]
4115
r
[5]
4035 r/w [6]
4116
r
[6]
4036 r/w [7]
4117
r
[7]
4037 r/w [8]
4118
r
[8]
Digital Outputs 1 to 8
Off (0)
On (1)
Event Output
Turn an event out-
put on or off. (Digital
outputs must be con-
figured in the Setup
Page before they can
be used here. Verify
that the setup
matches events.)
Active if digital inputs are config-
ured as wait for events.
4012 r/w
4103 r
Step does not
wait (0)
Step does not wait (0)
Step waits for…(1)
Wait for
Wait for an event or
process value. (Digi-
tal inputs must be
configured in the
Setup Page before
they can be used
here.) The F4 can be
programmed to wait
for up to 4 event in-
puts and 3 analog in-
puts.
…>Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Ramp Time or Ramp Rate or Soak Step
Ramp Time or Ramp Rate or Soak Step
Active: Always.
4009
4010
4011
r/w
00:00:00
[h] (0)
[m] (0)
[s] (0)
00:00:00 to 23:59:59
[h] (0 to 23)
[m] (0 to 59)
[s] (0 to 59)
Time
Set time to
autostart.
Active: Always.
4008 r/w
Every Day (0)
Every Day (0)
Sunday (1)
Monday (2)
Tuesday (3)
Wednesday (4)
Thursday (5)
Friday (6)
Saturday (7)
Day
Set day of the week
to autostart.
Active: Always.
4004 [Date]
or [Day]
4005
[mo]
4006 [day]
4007
[yr]
r/w
today’s date
M/D/Y
[Date] (0)
[Day] (1)
[mo] (1 to 12)
[day] (1 to 31)
[yr] (1998 to 2035)
Date
Set date to
autostart.
…>Edit Profile > Profile x (1 to 40) > Edit Step > Step x (1 to 256) > Autostart Step
Autostart