Setup page parameter table, Communications – Watlow Series F4S/D User Manual
Page 62
5 . 1 4
■
S e t u p
Wa t l o w S e r i e s F 4 S / D
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set, Ch)
Parameters to Appear
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set, Ch)
Parameters to Appear
✔ NOTE:
Press the Information Key
ˆ for more task-related tips.
Active: Always.
Not
available
1
1 to 247 (1 to 247)
Address
Select address for
controller.
Active: Always.
Not
available
19200
19200 (0)
9600 (1)
Baud Rate
Select transmission
speed.
Main > Setup > Communications
Communications
ç
WARNING: Provide a labeled switch or circuit breaker near peripheral equipment per-
manently connected to the Series F4 digital outputs as the means of disconnection for
servicing. Failure to do so could result in damage to equipment and/or property,
and/or injury or death to personnel.
Active if Digital 8 Function is
Compressor.
2074 r/w
30 seconds
(30)
1 to 9999 seconds
(1 to 9999)
Compressor On Delay
Set time to delay
compressor turn-on.
Active if Digital 8 Function is
Compressor.
2075 r/w
10 seconds
(10)
0 to 9999 seconds
(0 to 9999)
Compressor Off Delay
Set time to delay
compressor turn-off.
Active if Digital 8 Function is
Compressor.
2073 r/w
Compressor
on % power
Compressor on %
power to 100%
Compressor Off % Power
The compressor will
be off above this
chosen power level.
Active if Digital 8 Function is
Compressor.
2072 r/w
0% (0)
-100% to 100%
(-100 to 100)
Compressor On % Power
The compressor will
be on below this
chosen power level.