Setup page parameter table, Control output x (1a , 1b, 2a and 2b) – Watlow Series F4S/D User Manual

Page 59

background image

Wa t l o w S e r i e s F 4 S / D

S e t u p

5 . 1 1

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set, Ch)

Parameters to Appear

NOTE:
For more information about how parameter settings affect the con-

troller’s operation, see the Features Chapter.

Active: Always.

Output

715

[1A]

732

[1B]

749

[2A]

766

[2B]

r/w

0% (0)

0% to High Limit -1

(0 to High Limit -1)

Low Power Limit

Set low limit control

(PID mode only)

output power level.

Active: Always.

Output

714

[1A]

731

[1B]

748

[2A]

765

[2B]

r/w

100% (100)

Low Limit +1 to 100%

(Low Limit +1 to 100)

High Power Limit

Set high limit con-

trol (PID mode only)

output power level.

Active if the selected output is

set to a process output.

Output

701

[1A]

718

[1B]

735

[2A]

752

[2B]

r/w

4 to 20mA (0)

4 to 20mA (0)

0 to 20mA (1)

0 to 5V (2)

1 to 5V (3)

0 to 10V (4)

Process

Set process output

type.

Active if the selected output is

not Process and Burst is set to

No.

Output

506

[1A]

556

[1B]

2506 [2A]

2556 [2B]

r/w

Fixed Time

1.0 sec. (10)

.1 to 60

(1 to 600)

Enter Cycle Time

Select the duration

of cycle.

Active always.

Output

509

[1A]

559

[1B]

2509 [2A]

2559 [2B]

r/w

Variable Burst (0)

Fixed Time (1)

Choose Cycle Time

Enter the value of

the variable burst

cycle time.

Active if Analog Inputs 1 and 2

are enabled.

Output

700

[1A]

717

[1B]

734

[2A]

751

[2B]

r/w

Heat (1A and

2A) (1)

Off (1B, 2B)

(0)

Off (0)

Heat (1)

Cool (2)

Function

Select type of func-

tion for output.

Main > Setup > Control Output x (1A,1B, 2A and 2B)

Control Output x (1A,1B, 2A and 2B)

Active: Always.

Digital inputs are edge trig-

gered and require a transition

from high to low or low to high.

Input

1061

[1]

1063

[2]

1065

[3]

1067

[4]

r/w

Low (0)

Low (0)

High (1)

Condition

Select the condition

to trigger digital

input.

Active: Always.

While a profile is running, the

controller will not recognize

digital inputs that are pro-

grammed to start a profile.

Only one profile can be run at a

time.

* This prompt only appears if the

F4 memory contains a profile.

Input

1060

[1]

1062

[2]

1064

[3]

1066

[4]

r/w

Off (0)

Off (0)

Panel Lock (1)

Reset Alarm (2)

Control Outputs Off (3)

All Outputs Off (4)

Digital Outputs Off (5)

Start Profile (6)*

Pause Profile (7)

Resume Profile (8)

Terminate Profile (9)

Wait for Event (10)

Function

Select the digital

input function.