How to set up ratio control, Ratio control example: diluting koh, Set point of the ratio loop 74 – Watlow CPC400 User Manual
Page 88

Chapter 3: Operation and Setup
CPC400 Series User’s Guide
74
Watlow Anafaze
Doc. 0600-2900-2000
.
Figure 3.13 Relationship Between the Process
Variable on the Master Loop and
the Set Point of the Ratio Loop
NOTE!
Ratio control cannot be used on the same control
loop as cascade control.
How to Set Up Ratio Control
1.
Adjust and tune the master loop for optimal perfor-
mance before implementing the ratio setup.
2.
For the ratio loop, set the parameters in the Ratio
menu.
3.
Configure both the master loop and the ratio loop for
inputs, outputs, and alarms.
Ratio Control Example: Diluting KOH
A chemical process requires a formula of two parts water
(H
2
O) to one part potassium hydroxide (KOH) to produce
diluted potassium hydroxide. The desired flow of H
2
O is 10
gallons per second (gps), so the KOH should flow at 5 gps.
Separate pipes for each chemical feed a common pipe. The
flow rate of each feeder pipe is measured by a CPC400, with
H
2
O flow measured on loop 1 and KOH flow measured on
loop 2. The outputs of loops 1 and 2 adjust motorized
valves.
High SP
Low SP
Input Range
Input Range
Master PV * Control Ratio + SP Diff
erential
Ratio Loop Set P
oint
Master Loop Process Variable
SP Differential
SP = Set Point
PV = Process Variable
Low
High