Alarms Menu

Use the Alarms menu to configure high alarms, low
alarms, and deviation alarms, including:

Alarm set points

Alarm outputs

Alarm behavior

Alarm hysteresis

Alarm delay

Alarm High Set Point

Enter the set point at which the high alarm activates. The
high alarm activates if the process variable rises above this
value. For more information about the high alarm, see
Alarm High and Alarm Low on page 66.

Values: For a thermocouple or RTD input, any value with-
in the input range (see Table 5.7 on page 104). For a pro-
cess or pulse input, any value between the Input range low
and Input range high parameters.
Default: 1000. Decimal placement depends upon the Input
type
and Disp format settings.
Modbus Address (Loops 1 to 9): 40307 to 40315
Parameter Number: 18
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 18.1 to 18.9
Decimal Placement for Modbus or LogicPro: See Dec-
imal Placement for Numeric Values on page 80
.