113

Heat/Cool Filter

Use this parameter to dampen the response of the heat or
cool output. The output responds to a change by going to
approximately two-thirds of its final value within the spec-
ified number of scans. A larger value results in a slower re-
sponse to changes in the process variable.

Values: 0 (off) to 255
Default: 3
Modbus Address (Loops 1 to 9): 40239 to 40247 (heat) or
40256 to 40264 (cool)
Parameter Number: 14 (heat) or 15 (cool)
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 14.1 to 14.9 (heat) or
15.1 to 15.9 (cool)

Hysteresis

Specify how much the process variable must deviate from
set point before the output can switch between on and off
(for on/off control) or switch between heating and cooling
(for heat/cool control).

Values: See Table 5.13 for values and decimal placement.
Default: See Table 5.13
Modbus Address (Loops 1 to 9): 40856 to 40864
Parameter Number: 54
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 54.1 to 54.9
Decimal Placement for Modbus or LogicPro: See Dec-
imal Placement for Numeric Values on page 80
.

Table 5.13

Values for the Control Hysteresis
and Deviation Alarm Parameters

Input Type

Display Format

Values

Default

Thermocouple

n/a

0 to 500

5

RTD

n/a

0 to 500.0

5.0

Process or Pulse

-999 to 3000

0 to 500

5

-9999 to 30000

0 to 5000

50

-999.9 to 3000.0

0.0 to 500.0

5.0

-99.99 to 300.00

0.00 to 50.00

0.50

-9.999 to 30.000

0.000 to 5.000

0.050

-0.9999 to 3.0000

0.0000 to 0.5000

0.0050

l01 Heat filterr
b 3 scans

l01 Hysteresis r
b 5 ˚F