Heat/cool filter, Hysteresis – Watlow CPC400 User Manual
Page 127
CPC400 Series User’s Guide
Chapter 5: Menu and Parameter Reference
Doc. 0600-2900-2000
Watlow Anafaze
113
Heat/Cool Filter
Use this parameter to dampen the response of the heat or
cool output. The output responds to a change by going to
approximately two-thirds of its final value within the spec-
ified number of scans. A larger value results in a slower re-
sponse to changes in the process variable.
Values: 0 (off) to 255
Default: 3
Modbus Address (Loops 1 to 9): 40239 to 40247 (heat) or
40256 to 40264 (cool)
Parameter Number: 14 (heat) or 15 (cool)
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 14.1 to 14.9 (heat) or
15.1 to 15.9 (cool)
Hysteresis
Specify how much the process variable must deviate from
set point before the output can switch between on and off
(for on/off control) or switch between heating and cooling
(for heat/cool control).
Values: See Table 5.13 for values and decimal placement.
Default: See Table 5.13
Modbus Address (Loops 1 to 9): 40856 to 40864
Parameter Number: 54
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 54.1 to 54.9
Decimal Placement for Modbus or LogicPro: See Dec-
imal Placement for Numeric Values on page 80.
Table 5.13
Values for the Control Hysteresis
and Deviation Alarm Parameters
Input Type
Display Format
Values
Default
Thermocouple
n/a
0 to 500
5
RTD
n/a
0 to 500.0
5.0
Process or Pulse
-999 to 3000
0 to 500
5
-9999 to 30000
0 to 5000
50
-999.9 to 3000.0
0.0 to 500.0
5.0
-99.99 to 300.00
0.00 to 50.00
0.50
-9.999 to 30.000
0.000 to 5.000
0.050
-0.9999 to 3.0000
0.0000 to 0.5000
0.0050
l01 Heat filterr
b 3 scans
l01 Hysteresis r
b 5 ˚F